Defrost
– the NorAire controller has a unique energy boost function for the ODU defrost sequence. When the
ODU defrost wire goes high, the Electro-Boiler output is bypassed directly to the pump IN. As all of the
Electro-Boiler elements turn on, they are supplying warmer water directly to the heat exchanger (now an
evaporator) to boost the refrigerant energy for defrost. At the end of the defrost cycle this bypass tube is valved
off and the Electro-Boiler supply pipe is again connected to the “Heating Water OUT”.
During initial installation it is very important that there is no air in this bypass tube because it could
cavitate the pump, see Water Fill/Purge Procedure section (defrost boiler bypass).
Utility interrupt function or blue wires connection
– the PC setup and defaults control this input. If it is set at
“none” there will be no action from this terminal block connection.
Selection “Boiler” or “All” refers to the internal Electro-Boiler
The backup relay contact (K2) is
not
controlled by the utility interrupt. It is assumed this is for a gas
boiler.
If a mode C (and backup contact) it is an external Electro-Boiler and utility interrupt is required, the
utility device
must
have its own contact at the Electro-Boiler blue wire.
Low voltage fusing
– the control board has a temperature sensitive auto reset fuse (between J2 and adjacent
relay). If there is a 24VAC short external from the control board or at any internal R voltage circuit trace, this
will open. A DC power supply V+ or +5 volt short will not “blow” this fuse. The voltage regulator simply
opens up. These two DC voltages can be verified at the V+ tab (T7) and at the sensor RED screw, respectively.
Power must be off for at least 5 minutes to allow auto reset of this fuse.
ODU fault or troubleshooting
– each ODU has its own fault LED counts or indicators.
Internal 3-way valve actuators/knob –
for reference purposes this sketch shows the position of the 3-way
valves.
Summary of Contents for NC-FE series
Page 22: ...05 16 2014 20 NI216 ...
Page 49: ... 0 1 2 3 4 5 6 3 0 1 40 1 5 3 1 7 8 8 4 5 43 15 ...
Page 50: ... ...
Page 51: ... ...
Page 52: ... ...
Page 53: ... ...
Page 54: ... ...
Page 55: ... 01 2 ...
Page 56: ... 0 0 1 0 2 1 3 4 4 5 0 6 ...
Page 57: ... ...
Page 60: ......
Page 63: ...XX036 ...
Page 64: ...XX036 ...