background image

5

NookBox

Installation Guide

Smoke Mini Detector

Alarm Detection 

The Smoke Detector will activate fire alarm when either of its smoke detection or high heat detection function is triggered. When an alarm is 
activated, the Smoke Detector will transmit alarm signal and raise alarm with its built in buzzer, the Red LED will flash rapidly. The alarm sound 
will repeat in pattern of 3-second alarm and 1-second pause.

Smoke Detection:

•  The Alarm is activated whenever the smoke concentration exceeds the detection threshold.
•  The Smoke Detector will check some concentration every 8 seconds, the alarm will continue until the smoke concentration drops  

 

 

below alarm threshold.

Heat Detection: 

•  Rate of Rise: When the temperature rises by 8.25°C per minute.
•  High Heat: When the temperature exceeds 57.3°C

The Smoke Detector will check temperature every 10 seconds. It will only stop alarming if the temperature drops below alarm threshold:

•  If the alarm was triggered by Rate of Rise condition (8.25°C per minute or more): The temperature must drop to 4°C below highest 
 

temperature detected for the Detector to stop alarming.

•  If the alarm was triggered by High Heat condition (57.3°C): The temperature must drop below 49°C for Smoke Detector to stop 
 alarming.
•  For both Smoke alarm and Heat Alarm, a restore signal will be transmitted if no smoke is detected again for 160 seconds.

(Climax Control Panel Only)

The Smoke and Heat Detection function of the Smoke Detector can be disabled by sending ZigBee command from the Control Panel 
if needed to accommodate different installation environment. To disable the Smoke or Heat detection function:

1  Go to the Device List in the Control Panel setting, select “Edit Device” and find the “Bypass” option.
2  Before sending command from the Control Panel, press the Function Button on Smoke Detector once.
3  Select the function to be disabled from the Bypass option and confirm to send command. 

IR Detection:

•  The Smoke Detector will only transmit burglar alarm signal to the Control Panel if any movement is picked up within the IR 
 

detection coverage, the buzzer will not sound and the LED will not flash. (Please refer to your Control Panel for details).

Alarm Silence

•  After alarm activation, the Smoke Detector can be silenced temporarily by pressing the button.
 
 

1. 

If the button is pressed within 1 minute after alarm activation, the alarm will be silenced 1 minute after button press. E.g. If the button  

 

 

is pressed 30 seconds after alarm activation, then the alarm will be silenced at 1 minute and 30 seconds after alarm trigger.

 

2.  If the button is pressed when the alarm has been activated for more than 1 minute, the alarm silenced immediately and will enter  

 

 

 

Alarm Silence mode for 9 minutes.

•  The Alarm Silence mode lasts 9 minutes, the Red LED will flash every second during this period.
•  During the Alarm Silence period, f the smoke concentration or temperature continue to rise, the Smoke Detector will sound the alarm    
again and cannot be silenced by button press. The alarm condition must subside for the alarm to stop
•  When the 9-minute Alarm Silence period expires:
 

If the smoke concentration or temperature has dropped below alarm threshold, the Smoke Detector will sound a 2-tone beep and,  

 

 

transmits an alarm restore signal and returns to normal operation mode. 

 

If the smoke concentration or temperature is still above alarm threshold, the Smoke Detector will sound the alarm again.

Recalibration

As the operation condition of the Smoke Detector may vary after being installed for some time, you may wish to recalibrate the Smoke De-
tector to take a new smoke detection threshold value and ensure optimal performance of the Smoke Detector. To do this:

•  Press 20 seconds on the Test Button and hold until the Red LED starts to flash. The Smoke Detector will sound 3 short beeps then  

 

 

follow the calibration process to take the new reference value with the Red LED will flash every 2 seconds to indicate.

•  If calibration fails, the Smoke Detector will continuously beep with Orange LED flashing every second, you need to remove the 
 

battery, press the Test Button twice to fully discharge the battery, then reinsert the batteries to restart Smoke Detector.

•  Every time the battery is removed and reinserted, the Smoke Detector will also take the new threshold value following the warming  

 

 

and calibration process.

Summary of Contents for E6309676

Page 1: ...1 NookBox Installation Guide Smoke Mini Detector NookBox Smoke Detector Zigbee P119037 E6309676 Installation Guide...

Page 2: ...up mo vements within an assigned area and signals the Control Panel to activate the alarm if an intruder crosses its path of detection The Smoke Detector utilizes ZigBee technology for wireless signa...

Page 3: ...ange LED Flash every second Device power on Calibration failed Flashes every 5 seconds Detecting smoke failed or device malfunctioning Flashes every 4 seconds battery exhausted Flashes every 45 second...

Page 4: ...her dirty or out of order If the Red LED doesn t light and no beep is sounded it means the Smoke Detector is out of order Test Mode The Smoke Detector can be put into Test mode by pressing the Test Bu...

Page 5: ...overage the buzzer will not sound and the LED will not flash Please refer to your Control Panel for details Alarm Silence After alarm activation the Smoke Detector can be silenced temporarily by press...

Page 6: ...minutes the LED will continue to flash during calibration Joining ZigBee network is prohibited during warm up and calibration process After calibration process the Smoke Detector will emit a 2 tone be...

Page 7: ...e following locations In a ceiling area with full view of its detection coverage unobstructed by appliances and furniture Near the entrance of a room or house to monitor entry activity Limitations Do...

Page 8: ...s if required Step 4 Align the mounting holes on Smoke Detector with the hooks on the mounting bracket Fit the Smoke Detector onto bracket and rotate clockwise to lock the hook Installation is now com...

Page 9: ...ct mesh inside the chamber and clean the chamber and mesh with brush or water Step 4 Re insert the anti insect mesh into the chamber and insert the chamber back onto the Smoke Detector Please make sur...

Page 10: ...Read only Climax Technology O 0x0005 ModelIdentifier Character String 0 32 bytes Read only Model Number O 0x0006 DateCode Character String 0 16 bytes Read only O 0x0007 PowerSource 8 bit 0x00 0xff Rea...

Page 11: ...entifier Name Type Range Access Default Mandatory Optional 0x0000 MeasuredValue Signed 16 bit Integer Min Measured Value to Max Measure Value Read only 0x00 M 0x0001 MinMeasuredValue Signed 16 bit Int...

Page 12: ...12 NookBox Installation Guide Smoke Mini Detector For more information visit www getnookbox com...

Reviews: