5. Commissioning / Operation  ATTENTION

Filling

Ensure no fluid drips onto the pump motor or its electrical connections during installation,
venting or operation as when the pump is energised this may create a risk of electric shock.

In normal operation the pump surface can be hot (up to 125ºC) creating a risk of being burnt.

Water and water/glycol mixtures in the ratio of 1:1.

Glycol mixtures require a reassessment of pump hydraulic data in line with the increased
viscosity and depending on mixing ratios.

Use only approved makes of additives with corrosion inhibitors and follow manufacturer's
instructions.

Do not leave system empty without protection from corrosion inhibitor.

During this operation ensure the pump is switched off.

Open both valves either side of the pump.

Venting / Manual Restart

Protect all electrical parts against the leaking water

During this operation be aware of the risk of scolding from escaping hot water or steam.

When the system is filled with water the pump will normally self vent air within a short
while of switching on.

In cases where the pump venting is slow (identified by pump noise) the pump bearings may
be quickly vented by using: -

(a) the manual restart knob. Switch off the pump. Unscrew the manual restart Fig 3b

applying sideways pressure to the screw, with a screwdriver, until water emerges from it.
Screw the manual restart knob back in. Switch pump back on

(b) vent plug Switch off the pump. Close valve on the discharge side. Carefully loosen and

fully remove the vent plug with a suitable screwdriver Fig 3a , carefully push pump shaft
back several times with screwdriver. Switch on pump. It is possible that the pump blocks
with the vent plug open, depending on the system pressure. After 15 – 30 s tighten the
vent plug. Reopen the valve

Note, a system may take 24 hours to vent all the air in the system to atmosphere

ATTENTION

DO NOT run the pump dry as this will result in bearing failure.

Speed Regulator – Standard Pumps

Speed regulator adjustment should only be made with electrical supply 
switched off

Models offer a single or variable speed setting to allow system requirements to be accurately
met. Fig 4a

11

GB

8573 Nocchi Booklet 12 linguil 4124349:Pentair Water Italy Srl - Reb

Summary of Contents for R2SE

Page 1: ...uik en 32 onderhound 38 Manual de utilizi o e manuten o 44 K itt ja kunnssapito 50 Bruks och underh lls anvisningar 56 Uputsvo za upotrebu i odrzavanje 62 Instruksjonsh ndbok og vedlikehold 68 I F GB...

Page 2: ...sabilit que les produits de la s rie SR3 R2SE sont conformes aux Conditions Essentielles de S crurit et de Tutelle de la Sant selon les Directives 98 37 73 23 89 336 et leurs modifications suivantes P...

Page 3: ...iceras i direktiven 98 37 73 23 89 336 och senare till gg SR3 R2SE PENTAIR PUMPS S p A intygar under sitt eget ansvar att elpumparna nedan SAMSVARSERKL RING Firmaet Pentair Water Italy Srl erkl rer un...

Page 4: ...domestic central heating systems only 1 2 Product Data SR3 xx 40 SR3 xx 50 SR3 xx 60 SR3 25 70 R2SE ConnectionVoltage 1 230V 10 50Hz 1 230V 10 50Hz 1 230V 10 50Hz Insulation class H 1800 C H 180 C F 1...

Page 5: ...for earthing the outer casing is provided Standard Pumps Models offer a single or variable speed setting to allow system requirements to be accurately met Electronic Pumps The pump control channel is...

Page 6: ...ng a pump maintain the same direction of flow 4 3 Electrical Connections ATTENTION Electrical work to be carried out by a competent qualified and licensed electricians in strict conformity to ruling n...

Page 7: ...ent air within a short while of switching on In cases where the pump venting is slow identified by pump noise the pump bearings may be quickly vented by using a the manual restart knob Switch off the...

Page 8: ...guarantee efficient operation of the heating installation and optimum adaptation of the pump to the load on the hydraulic installation it is important to select the right control range The pump contro...

Page 9: ...ressure within the permissible limits Pump may require 48 hours to attain normal quiet operation Locked Pump Should the pump fail to start switch to maximum setting If the pump still does not start th...

Reviews: