pmg4111a0600p_01
13 / 24
7.5.2
C
ONTROL
P
ARAMETERS
Normal (measurement) mode
Setting the control parameters
3 s
P
ROGRAMMABLE
C
ONTROL
P
ARAMETERS
Select SV-2 (internal set value) within input range for each sensor.
SV-2 is effective if the IN
2
input is active.
Set alarm relay operation value (if alarm relay mode is selected in
).
(sec)
Set the output delay time for loop break alarm (0 … 999 s)
(if
is selected in
)
.
(°C)
.
Set the value of alarm hysteresis
(interval between ON and OFF for alarm output)
.
(%)
.
Set the value of Proportional band in %
If value of
is set to
.
the unit operates in ON/OFF mode
(sec)
Set the value of Integral time in seconds
If value of
is set to
this function will be OFF
(sec)
Set the value of Derivative time in seconds
If value of
is set to
this function will be OFF
(sec)
Set the value of proportional control cycle time in seconds
In case of SSR output this value should be small, for example 2 sec.
.
(°C)
.
Set the value of switching difference
in case of ON/OFF control
.
(°C)
.
Set the correction value for input sensor error
Also suitable as an offset function for calibration
.
(%)
.
Set the value of manual reset (offset for the Proportional band) in %
(for
control only)
(min)
Set the value of RAMP rising time (in case of heating)
Only when
function is
(enabled)
(min)
Set the value of RAMP falling time (in case of cooling)
Only when
function is
(enabled)
Turning OFF the key lock
When the key lock is active the configuration cannot be changed
When ON1 is selected only the mode settings and auto-tuning is locked