21 / 28
5.3.4.3
Temperature simulation
This function helps the user to check the outputs and the connected processing units
After finished editing the settings, the unit must be returned into Measurement mode to start the simulation.
Temperature simulation mode
Parameter: P84:
a
Menu path:
SERVICE / TEMP. SIMULATION / MODE
Default value:
0
Description: Simulation
mode:
OFF
No PV simulation
FIX VALUE
Simulation value is according to the sum of the bottom value of
the simulation and the number of the sensor
TRIANGLE WAVE
The simulated value changes linearly between the set low and
high values with an adjustable cycle time
PV: Primary Value
SQUARE WAVE
The simulated value jumps between the set low and high
values within an adjustable cycle period