NIVELCO NIPRESS P6 Installation And Programming Manual Download Page 10

jbdp612a0600p_02

 10 / 12 

 

Menu 14 – Switch off delay SP 2 

 

Via the menu “Switch-off delay” it is possible to set the delay time of set point 2. Setup mode is entered by pressing both buttons simultaneously. 
You can set the required value by using the buttons “▲“ or “▼“.The delay time can be set between 0.01 and 90 seconds. To complete the 
setting push the two buttons simultaneously. 

Menu 15 – Teach – Switch-on point SP 1 

Via the menu “Teach switch-on point” the currently existing reference pressure in the pressure switch can be “taught” as switch-on point 1. For 
the teaching-operation you have to push both buttons simultaneously. Then “ref” will appear in the display and you have to connect the 
reference pressure on the pressure port of the switch. Is the reference value correct, accept it by pushing the two buttons simultaneously and 
the value will be stored in the pressure switch. 

Menu 16 – Teach – Switch-off point SP 1 

 

Via the menu “Teach switch-off point” the currently existing reference pressure in the pressure switch can be “taught” as switch-on point 1. For 
the teaching-operation you have to push both buttons simultaneously. Then “ref” will appear in the display and you have to connect the 
reference pressure on the pressure port of the switch. Is the reference value correct, accept it by pushing the two buttons simultaneously and 
the value will be stored in the pressure switch. 

Menu 17 – Teach – Switch-on point SP 2 

Via the menu “Teach switch-on point” the currently existing reference pressure in the pressure switch can be “taught” as switch-on point 2. For 
the teaching-operation you have to push both buttons simultaneously. Then “ref” will appear in the display and you have to connect the 
reference pressure on the pressure port of the switch. Is the reference value correct, accept it by pushing the two buttons simultaneously and 
the value will be stored in the pressure switch. 

Menu 18 – Teach – Switch-off point SP 2 

 

Via the menu “Teach switch-off point” the currently existing reference pressure in the pressure switch can be “taught” as switch-on point 2. For 
the teaching-operation you have to push both buttons simultaneously. Then “ref” will appear in the display and you have to connect the 
reference pressure on the pressure port of the switch. Is the reference value correct, accept it by pushing the two buttons simultaneously and 
the value will be stored in the pressure switch. 

Menu 19 – Loading of stored configurations 

 

Via the menu “Load“ it is possible to transfer up to five in P6 stored configurations into the pressure switch. During the transmitting the 
programming device checks whether the pressure switch matches with the configuration data. This approach shall make sure that the 
configuration data can be processed by the pressure switch. To start transfer of the desired configuration first both keys must be pressed 
simultaneously. Afterwards it is necessary to select one of the five configuration memories by pressing one of the keys until the desired memory 
(Loa1 till Loa5) is displayed. After the selection of the desired memory location the take-over of the data is started by pressing both buttons 
simultaneously. During the data transfer the display will be out of function and the green LED will indicate the data stream from the pressure 
switch. 

Summary of Contents for NIPRESS P6

Page 1: ...Manufacturer H 1043 Budapest Dugonics u 11 Phone 36 1 889 0100 Fax 36 1 889 0200 sales NIVELCO Process Control Co E mail nivelco com www nivelco com NIPRESS P6 programming device...

Page 2: ...NSTALLATION AND WIRING 3 2 1 GENERAL NOTES 3 2 2 STEPS OF INSTALLATION 3 2 3 WIRING 4 2 4 DIMENSIONS 5 3 PROGRAMMING 6 3 1 OPERATING AND DISPLAY MODULE 6 3 2 CONFIGURATION 6 3 3 STRUCTURE OF THE MENU...

Page 3: ...rogramming device P6 with integrated cable operating manual 2 INSTALLATION AND WIRING 2 1 GENERAL NOTES Please note that this device is a sensitive programming kit Handle the device carefully so that...

Page 4: ...e plug on the programming device Female plug on end of cable for DK 100 M 8 x 1 4 pin plastic for DK 200 M 12 x 1 5 pin plastic for DK 100 M 8 x 1 4 pin plastic for DK 200 M 12 x 1 5 pin plastic Suppl...

Page 5: ...jbdp612a0600p_02 5 12 2 4 DIMENSIONS Programming device P6 front and side view Programming device P6 view from above...

Page 6: ...help of two miniature push buttons located in the front button with this button you move forward in the menu system or increase the displayed value button with this button you move back in the menu s...

Page 7: ...PS Switching mode of contact 1 Menu 3 H 1 y CP 1 Switching mode of contact 1 Menu H 4 y 2 CP2 Contact 1 n o 5 S1on Menu Contact 1 ff o 6 S1of Menu Contact 2 n o 7 S2on Menu Contact 2 off S2o Menu 8 f...

Page 8: ...h buttons simultaneously setup mode is entered To select the desired function it is necessary to press or buttons until the desired function is displayed To finish the configuration and to store the s...

Page 9: ...t negation it is possible to invert the output signal of set point 2 Setup mode is entered by pressing both buttons simultaneously To select between standard not inverted signal S2St and inverted sign...

Page 10: ...ch on point 2 For the teaching operation you have to push both buttons simultaneously Then ref will appear in the display and you have to connect the reference pressure on the pressure port of the swi...

Page 11: ...2 Showing the low limit of the measuring range When the menu Lo r is active it is possible to display the low limit of the measuring range of the pressure switch The low limit is displayed for two sec...

Page 12: ...sible dirt deposited should be cleaned off All repairs will be carried out at the Manufacturer s premises 5 WARRANTY NIVELCO provides warranty of 3 three years in compliance with details described in...

Reviews: