Electrical connection unit
Power supply
The power supply, including the safety switch, must be installed by a certified electrician.
Connect the unit to N+J.
See also the wiring diagram supplied with the unit.
Unit
The illustration shown is for a left-facing version:
Power supply
3x400V 50HZ
Safety switch
Safety switch
Power supply (only for electric-heating surface, illustration shows without water-heating surface)
3x400V 50HZ
Ampere consumption depending on selected compressor and fans:
Unit
Compressor*
Fan (2 motors) total **
MTZ
VTZ
at 500 Pa
at 1000 Pa
[Amp]
[Amp]
[Amp]
[Amp]
VPM 600
21
21
4.0
6.2
VPM 700
24
24
4.4
7.6
VPM 800
28
30
6.3
8.3
VPM 1000
31
36
8.3
11.1
VPM 1200
42
44
8.2
14.3
VPM 1500
54
58
10.5
20.5
VPM 2200
67
72
20.5
28.7
* Depending on MTZ / VTZ compressor (configuration dependent).
** Ampere consumption on fan motors depending on air volume and pressure loss. Calculated based on
nominal air volume at final pressure loss external pressure loss = 500Pa and 1000Pa respectively
VPM 600-2200 (English)
BY NILAN
25