Installation
Positioning the unit
Good clearance in front of the unit is recommended (see table below). When positioning the unit, you
should always consider future service and maintenance. It must be easy to replace filters and it must be
possible to replace fans or other components. There must be enough space to clean the unit easily.
There must therefore be space for installing water traps in the condensate drains.
X
X = Recommended service distance.
Unit
X (in mm)
VPM 600
750
VPM 700
750
VPM 800
750
VPM 1000
750
VPM 1200
800
VPM 1500
800
VPM 2200
950
The unit must be level to enable proper drainage from the condensate tray.
The unit produces limited noise and vibrations, but you should still take into account potential vibrations
that can spread from the unit to individual parts of the building. In order to separate the unit from the
underlying surface, it is therefore recommended that you fit vibration absorbers under the unit. There
should be approx. 10 mm distance to other building components and to permanent fixtures.