9
Capacity - Heating element (accessory)
Electrical heating element
The electrical heating element is fitted in the air inlet duct at a distance of min. 2 x duct
diameter from the system´s fresh air inlet connection pipe (normally min 400 mm.)
and connected to the CTS 602 control panel and 230 V supply.
The electrical heating element can supply up to 3,0 kW of heat.
Water heating element for internal fitting
The water heating element is designed to be built into the system and must be
connected to the primary heating supply and the CTS 602 control. The water heating
element includes copper pipes and aluminium fins.
Capacities can be seen in the table below.
Water side
Air side
Temperature
input/output
[°C]
Flow
[m
3
/h]
Pressure drop
[kPa]
Output
[kW]
Flow
[m
3
/h]
Temperature
before WHE*
[°C]
Temperature
after WHE*
[°C]
Pressure drop
over WHE*
[Pa]
40/30
0.1
0.74
1.1
200
16
32.2
2
0.12
1.11
1.4
270
16
30.9
3
0.16
2.1
1.9
420
16
29.2
4
0.21
3..2
2.5
620
16
27.7
8
60/40
0.09
0.6
2
200
16
45.4
2
0.11
0.9
2.5
270
16
43.1
3
0.15
1.6
3.4
420
16
40
4
0.2
2.5
4.5
620
16
37.2
8
70/40
0.07
0.36
2.3
200
16
49.4
2
0.08
0.53
2.8
270
16
46.6
3
0.11
0.92
3.9
420
16
42.9
4
0.14
1.47
5
620
16
39.6
8
Capacity water heating element
* Water heating element.