Date: ___________________________________________
Tag: _____________________Qty:___________________
Project: _________________________________________
Engineer: _______________________________________
Contractor: ______________________________________
Supplier: ________________________________________
Quote#: _________________________________________
Submitted by: ____________________________________
49 "
(1245)
STALE AIR
TO OUTSIDE
FRESH AIR
TO INSIDE
14 3/4"
(375)
19" (483)
Por ts
7" (178 mm)
CONDENSATE
DRAINS
BLOWERS
*NOTE:
Front clearance of 25 inches (635 mm)
is recommended for ser vicing unit.
MOTOR
FRESH AIR
FROM OUTSIDE
STALE AIR
FROM INSIDE
FILTER
DEFROST
DAMPER
DEFROST AIR
FROM INSIDE
FILTER
Por ts
6" (150 mm)
METAL CLASPS
EN
G
INEERIN
G
DATA
THERMALL
Y C
ONDU
C
TI
V
E
, P
ATENTED
ALUMINUM
C
ORE
The cross-flow heat recovery core transfers heat between the two airstreams. The two
cores are arranged for highly efficient counter current airflow.
MOTORS
AND
B
LO
W
ERS
Each air stream has one centrifugal blower driven by a common ECM motor. 5 speed
fan operation. 120 VAC, 1.4 Amps.
FILTERS
Washable air filters in exhaust and supply air streams.
MOUNTIN
G
THE
HR
V
Four threaded inserts at corners of case designed to accept four reinforced polyester
straps that are supplied with the unit.
DEFROST
Damper defrost system.
DEHUMIDISTAT
Adjustable Internal Dehumidistat.
C
ASE
Twenty gauge prepainted galvanized steel (G60) for superior corrosion resistance.
Insulated to prevent exterior condensation. Drain connections 2 - 1/2" (12 mm) OD.
C
ONTROLS
ControlAir 15 - Standby/ON mode, 20 ON/ 40 OFF mode (each mode has 5 speeds).
Control pad can be removed from HRV and remotely mounted.
Weight
106 lbs. (48 kg)
S
hipping Weight
108 lbs. (49 kg)
A
ll
units
conform
to
CSA
and
UL
standards.
M
odel 195
E
C
M
DIMENSIONS
195
E
C
M
inches
(mm)
*S
ensi
b
le
E
fficienc
y –
thermal
**L
atent
E
fficienc
y –
moisture
Note: Effectiveness - based on temp. differential between the 2 airstreams
Efficiency – takes into account all power inputs
Performance
N
et
su
pp
l
y
air
flo
w
in
cfm
(
L/
s)
against
e
x
ternal
static
p
ressure
E
.S.P
(external static pressure)
[cfm (L/s)]
@ 0.1" (25 Pa)
171 (81)
@ 0.2" (50 Pa)
164 (77)
@ 0.3" (75 Pa)
156 (74)
@ 0.4" (100 Pa)
143 (67)
@ 0.5" (125 Pa)
134 (63)
@ 0.6" (150 Pa)
126 (59)
@ 0.7" (175 Pa)
119 (56)
Max. Temperature Recovery
88%
Sensible Effectiveness
@ 114 cfm (54 L/s)
32°F (0°C)
88%
*Sensible Efficiency
@ 114 cfm (54 L/s)
32°F (0°C)
81%
*Sensible Efficiency
@ 119 cfm (56 L/s)
-13°F (-25°C)
77%
VAC @ 60HZ
120
WATTS / Low speed
34
WATTS / High speed
95
Amp rating
1.4
20
40
60
80
100
120
140
160
180
200
220
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
S
tatic
Pre
ssu
re
(
in
w.
g
.)
A
ir
F
lo
w (
cf
m
)
O
P
TIONAL
MAIN
C
ONTROLS
99-350
L
ife
s
tyle Ventilation Control
7/24 programmable ventilation, (3 wire) 20
gauge wire (min.) 100’ length
99-109
A
ir
S
entry
A
ir Q
u
ality
M
onitor
designed to accept remotely mounted
Control Pad, (3 wire) 20 gauge wire (min.) 100’ length
99-250
Ventilation
D
eh
u
midi
s
tat
designed to accept remotely mounted Control
Pad, (4 wire) 20 gauge wire (min.) 100’ length
O
P
TIONAL
TIMERS
99-104
D
igital
E
lectronic
T
imer
- initiates high speed ventilation for 20, 40 or 60
minutes, (3 wire) 20 gauge wire (min.) 100’ length
99-101
Crank
T
imer
- Initiates high speed ventilation for up to 60 minutes, (2 wire)
20 gauge wire (min.) 100’ length
O
P
TIONAL
A
CC
ESSORIES
99-163
Du
ct
H
eater
w/
E
lectronic
S
C
R
T
hermo
s
tat,
1 Kw, 6” (150 mm)
99-164
Du
ct
H
eater
w/
E
lectronic
S
C
R
T
hermo
s
tat,
2 Kw, 6” (150 mm)
99-185
Weatherhood
s
, Two - 6” (150 mm) c/w 1/4” (6 mm) mesh screen
W
ARRANT
Y
Units carry a LIFETIME warranty on the heat recovery core and a 5 year replacement
parts warranty.
T
he
E
C
M
motor
prod
u
ce
s
a
tone
that
s
ome
may
find
o
bj
ectiona
b
le
.
We
recommend
the
in
s
tallation
of
the
optional
99-
SILEN
C
ER
6
on
the
‘S
tale
A
ir
from
I
n
s
ide
’
and
‘F
re
s
h
A
ir
to
I
n
s
ide
’
d
u
ct
s.
ATTENTION
TI-195ECM