C. Setting maximum 'max'
In programming mode, to go from ‘min’ to ‘max’, briefly press the
programming button. The load dims up to the set maximum. You can set
the max. dimming intensity in the section ‘max’. The maximum dimming
intensity can adopt any value between 60% and 100%.
Proceed as follows (see next diagram):
- Place the analog control in the section ‘max’ of the programming
mode: LED ‘max’ blinks.
- Set the desired max. intensity using the ‘select’ button or the connected
control. Keep the button pressed to dim up to 100% or down to 60%.
To reverse the dimming direction, let go of the button and immediately
press it again. When the desired intensity has been reached, let go
of the 'select' button or the connected control.
keep pressed = dim up
let go and then keep pressed = dim down
Press the programming button >2s to save the settings and exit
the programming mode. For other settings, briefly press the ‘select’
button. The analog control then returns to the programming section
‘input’ (3.A).
EN
prog
select
prog
prog
> 2s.