Electric Power Generation 

l

Installation and maintenance 

1

5874 en - 2020.01 / a 

TALA40 

Low Voltage Alternators - 4 pole 

• Checking the winding

You  can  check  the  winding  insulation  by 

performing a high voltage test. ln this case, 

you must disconnect all AVR wires. 

[WARNING] 

conditions  is  not  covered  by  our 

warranty. 
• Checking the diode bridge

A diode in good working order should allow 

the  current  to  flow  only  in  the  anode-to­

cathode direction. 

Anode 

0

._;

__.

.,_

1

-

---

� 

Cathode 

J

IN 

IN 

• Checking the windings and rotating

diodes using separate excitation

During  this  procedure,  make  sure  that 

the alternator is disconnected from any 

external  load  and  inspect  the  terminal 

box  to  check  that  the  connections  are 

fully tightened. 

1) Stop the unit, disconnect and isolate the

AVR wires.

2) There  are  two  ways  of  creating  an

assembly with separate excitation.

Assembly  A: 

Connect  a  12  V  battery  in 

series  with  a  rheostat  of  approximately 

50 ohms - 300 W and a diode on bath exciter 

field wires (5+) and (6-). 

ASSEMBLY A 

6 _  Field 

5+ 

Rh. 50 -300W 

Assembly  B: 

Connect  a  "Variac"  variable 

power  supply  and  a  diode  bridge  on  bath 

exciter field wires (5+) and (6-). 

Bath  these  systems  should  have 

characteristics  which  are  compatible  with 

the  field  excitation  power  of  the  machine 

(see the nameplate). 

3) Run the unit at its rated speed.

4) Gradually  increase  the  exciter  field

current  by  adjusting  the  rheostat  or  the

variac and measure the output voltages on

L 1 - L2 - L3, checking the excitation voltage

and  current  at  no  load  (see  the  machine

nameplate or ask for the factory test report).

When the output voltage is at its rated value

and  balanced  within  1 %  for  the  rated

excitation  level,  the  machine  is  in  good

working  order.  The  fault  therefore  cornes

from  the AVR or  its  associated  wiring  (ie.

sensing, auxiliary windings).

ASSEMBLY B 

6 _  Field

5+ 

DC 

12V 

LEROY-SOMER'" 

17 

Summary of Contents for LEROY-SOMER TAL A40

Page 1: ......

Page 2: ...attention to the following 2 safety measures which must be complied with a During operation do not allow anyone to stand in front of the air outlet guards in case anything is ejected from them b Do n...

Page 3: ...tics 5 3 1NSTALLATION 9 3 1 Assembly 9 3 2 Checks prior to first use 10 3 3 Terminal connection diagrams 10 3 4 Commissioning 13 3 5 Setting up 13 4 SERVICING MAINTENANCE 14 4 1 Safety measures 14 4 2...

Page 4: ...e machine conforms to your order So that you can identify your alternator quickly andaccurately we suggest you fill in its specifications on the nameplate below A A g CE OC AU4 1 a S j 151JJl5 2 J f r...

Page 5: ...ent single bearing with standard feet and SAE flanges coupling dises Drip proof machine self coole Electrical options Space heaters ln order to conform to standard EN 61000 6 3 EN 61000 6 2 EN 55011 t...

Page 6: ...R Armature Exciter field Y 0 ro 0 MAIN FlELD Rotating reclifiers T1 U1 T4 U2 ellow reen blue For del a conneciion 1PH 3PH T2 V1 C C l T5 V2 tl C C C C 0 0 8 C L C b 8 use termlnals N and U conneci N a...

Page 7: ...N FUELD STATOR 12 wire T1 to T12 identification EXCllER Armature Exctter eld t IRata ting redifiers i 0 i C Onsu lt R12 i j C r 1 UI i 1 C N 3P 1 PH D A F FF btue Tl O TI TI T1D ye low T1l 711 T1 T1 l...

Page 8: ...L M 6 5 g C I r s 10 2 1 r 81 71 Sl P1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 _ J 1 1 STATOR Op iio n lili POUrT AL 044 seul O o nalr J CT forTAL 044 onty STATO R 6 fflSM i s Jma i T1 fu T6 1104 su oo T4 3 PH 1...

Page 9: ...ity and the environment of the machine During this operation do not allow anyone to stand under the load After handling the machine using the lifting ring snap on the plastic cover provided in the mai...

Page 10: ...e working continuously while the machine is stopped WARNING Ensure that the alternator has the degree of protection matching the defined environmentalconditions Mechanical checks Before starting the m...

Page 11: ...0 0 0 0 0 0 T6 L3 W L2 V Ll U L3 W L L2 V L L1 U 5874 en 2020 01 a Connectio ncodes Voltage Detection FactorryconnecUon 3PHI Star 1 U Winding 50 Hz so Hz Ol m rs TO THE RIGH1 01 TPUTS TO THE LEFT 6S 3...

Page 12: ...T3 _ __fa V 2 L2 T2 U 1 L1 T1 NDE DE N N T10 U T1 N1 n c V T2 T5 W 3 L3 V 2 L2 U 1 L1 L1 U Series Delta L3 W L M VoltageLM 1 2voltageLL L VoltageLM 1 2voltageLL 1PH or 3PH L L lh Winding 6 8 AREP R180...

Page 13: ...wn in the terminal connection diagram The alternator earth terminal inside the terminal box is connected to the electrical earth circuit The earth terminal is connected to the frame The connections in...

Page 14: ...ectrical connections in the installation Electrical servicing Commercially available volatile degreasing agents can be used WARNING Do not use trichlorethylene perchlo rethylene trichloroethane or any...

Page 15: ...gged or hot air is being Abnormal alternator frame more than recycled from the alternator or engine temperature 40 C above the ambient Alternator operating at tao high a voltage 105 of Un on temperatu...

Page 16: ...nce Speed tao low lncrease the drive speed do not touch theAVR voltage pot before running at the correct speed Voltage AdjustAVR volt Adjustment ineffective FaultyAVR tao high age potentiometer Voltag...

Page 17: ...ly with separate excitation Assembly A Connect a 12 V battery in series with a rheostat of approximately 50 ohms 300 Wand a diode onbathexciter field wires 5 and 6 ASSEMBLY A 6 _ Field 5 Rh 50 300W As...

Page 18: ...ghtening torque See section 5 4 The bolts for fixing the feet on the housing and immobilising the stator must not be removed boit of the stator lower Access to connections and the regulationsystem The...

Page 19: ...insert a tube of the corresponding diameter on the shaft end or a support made according the following bellow Rest the rotor on one of its pales then siide it out Use the tube as a lever arm to assist...

Page 20: ...lues consult the test report and are subject to change without priorwarning Three phase 4 pole SHUNT excitation 6 and 12 wire Resistances at20 C l Type L N Rotor Field stator coil C 0 776 3 050 14 1 D...

Page 21: ...X2 auxiliary Z1 Z2 auxiliary windings windings C 0 452 0 375 D 0 364 0 311 E 0 377 0 326 F 0 342 0 356 G 0 318 0 330 Tableofweights values given for information only Three phase SHUNT AREP 6 and 12 wi...

Page 22: ...type its serial number and the information given on the nameplate Address your enquiry to your usual contact Part numbers should be identified from the exploded views and their description from the p...

Page 23: ...ic Power Generation 1 Installation and maintenance 1 TALA40 Low VoltageAlternators 4 pole 5 4 Exploded view parts list and tightening torque Single bearing SHUNT orAREP Il w LEROY SOMER 5874 en 2020 0...

Page 24: ...15 1 Fan M5 4 90 1 Exciter field stator 28 1 Earth terminal 91 4 Fixing bolts M6 10 30 1 Drive end DE 100 1 Exciter armature rotor shield 33 1 Protective guard M5 4 124 1 Terminal block 36 1 Non driv...

Page 25: ...s Our technical support depar tment can provide detailed directions on products dismounting upon request Waste hazardous materials The following components and materials need a special treatment and n...

Page 26: ...Electric Power Generation 1 Installation and maintenance 1 5874 en 2020 01 a TALA40 Low VoltageAlternators 4 pole 26 LEROY SOMER...

Page 27: ......

Page 28: ...din com company leroy somer Twitter com EPG_Alternators Facebook com LeroySomer EPG YouTube com LeroySomerOfficiel Nld c Il for dreams TM LEROY SOMER www leroy somer com epg lm rJ 11 l l 5874 en 2020...

Reviews: