3.2 - Checks prior to first use
• Electrical checks
Under no circumstances should an
alternator, new or otherwise, be operated
if the insulation is less than 1 megohm
for the stator and 100,000 ohms for the
other windings.
There are 2 possible methods for restoring
the above minimum values.
a) Dry out the machine for 24 hours in a
drying aven at a temperature of 110 °C
(without the regulator).
b) Blow hot air into the air intake, having
made sure that the machine is rotating with
the exciter field disconnected.
Note: Prolonged standstill
ln order to avoid these problems, we
recommend the use of space heaters, as
well as turning over the machine from time to
time. Space heaters are only really effective
if they are working continuously while the
machine is stopped.
[WARNING]
Ensure that the alternator has the degree
of protection matching the defined
environmental conditions.
• Mechanical checks
Before starting the machine for the first time,
check that:
- all fixing bolts are tight,
- the length of boit and the tightening torque
are correct,
- the cooling air is drawn in freely,
- the protective grills and housing are cor-
rectly in place,
- the standard direction of rotation is clock
wise as seen from the drive end (phase
rotation in order 1 - 2 - 3).
- the winding connection corresponds to the
site operating voltage (see section 3.3).
3.3 -Terminal connection diagrams
To modify the connection, change the
position of the statorcables on the terminais.
The winding code is specified on the
nameplate.
�
Any intervention on the alternator
terminais du ring reconnection or checks
should be performed with the machine
stopped.
ln no case should the internai
connections in the terminal box be
subjected to stresses due to cables
connected by the user.