2018.01 / g

9

Electric Power Generation

Installation and maintenance

R150

AVRs

5384 en -

8 - MULTIMETER CHECKS

Equipment: Digital multimeter.

Select Diode mode on the digital multimeter. 

The resistance between F1 and F2 (with the 

multimeter jack common applied to F1 of the 

AVR) should be between 0.4 and 0.6 V, and 

vice versa (with the multimeter jack 

common applied to F2 of the AVR) should 

give 

INFINITY

.

ZERO

 indicates a power device failure in 

both cases. No further tests (static or 

dynamic) are allowed, as they would lead to 

the fuse blowing.
The resistance between F2 and U (both 

sides) should be 180 k

W

.

The resistance between F2 and V (with the 

multimeter jack common applied to the AVR 

V terminal should be approximately 2. 2 M

W

 

in the 10 M

W

 range and vice versa (with the 

multimeter jack common applied to the AVR 

F2 terminal) should be 15 M

W

.

ZERO

 indicates power device failure in both 

cases. No further tests (static test or dynamic 

tests) are allowed, as they would to the fuse 

blowing.
The resistance between U and V should 

be 300 k

W

 to 400 k

W

. Open circuit indicates 

AVR failure. During a static test the lamp will 

not  turn  OFF  or,  when  connected  to  the 

generator it will produce ceiling voltage (for 

3-phase ONLY).

The resistance between U and N1 should be 

between 200 k

W

 and 260 k

W

. Open circuit 

indicates AVR failure.
During a static test, the lamp will not turn 

OFF or, when connected to the generator, it 

will produce a ceiling voltage (for 1-phase 

ONLY).
The resistance between N and F1 should be 

very low or ZERO ohms. If the circuit is 

open, the lamp will not glow when the static 

test is performed.

Summary of Contents for LEROY-SOMER R120

Page 1: ...R2 Droop 50 Hz V AC S UF OE SL UF OE 60 Hz R1 A1 A2 Q2 Q1 F2 F1 N FUSE W V R150 R150 AVRs Installation and maintenance...

Page 2: ...rning symbol for electrical danger to personnel All servicing or repair operations performed on the AVR should be undertaken by personnel trained in the commissioning servicing and main tenance of ele...

Page 3: ...IN FUNCTION OF THE AVR 6 5 AVR SETTINGS 7 5 1 V TRIM V 7 5 2 FRO UF 7 5 3 STAB S 7 5 4 EXC LIMIT OE 7 5 5 QUADRATURE DROOP 7 5 6 A1 A2 DC VOLTAGE INPUTS AC 7 6 AVR CONTROLS 7 7 TROUBLESHOOTING CHART 8...

Page 4: ...circuit continuously monitors the generator underspeed protection by reducing the generator output voltage in proportion with the speed below a threshold The AVR has the facility for droop CT connecti...

Page 5: ...ge regulation 0 8 at the AVR terminals 14 Thermal drift 1 for a 30 C change in temperature 15 Response time less than 50 ms 16 Closed loop response typically 0 5 sec to recover 98 of the defined volta...

Page 6: ...sects the amplified voltage at a point which is early or late in the half cycle At this intersection point a starting pulse is produced to trigger the power device Only qualified personnel should repl...

Page 7: ...r clockwise will result in a sluggish response and possibly also oscillations The factory default setting is slightly higher than critical damping around halfway 5 4 EXC LIMIT OE This function is prov...

Page 8: ...oltmeter on the front defective Check and correct AVR defective repeated fuse blowing Replace after performing a static test Earthed exciter field Check and correct High voltage build up Loose or miss...

Page 9: ...hould be approximately 2 2 MW in the 10 MW range and vice versa with the multimeter jack common applied to the AVR F2 terminal should be 15 MW ZERO indicates power device failure in both cases Nofurth...

Page 10: ...ockwise the lamp should go out slowly Now turn the UF potentiometer clockwise The lamp should glow brightly again 5 It is difficult to prescribe a static test for checking the stability as this is mor...

Page 11: ...1 g 11 Electric Power Generation 135 mm 115 mm 110 mm 90 mm 10 10 R2 Droop 50 Hz V AC S UF OE SL UF OE 60 Hz R1 A1 A2 Q2 Q1 F2 F1 N FUSE W V R150 Installation and maintenance R150 AVRs 5384 en 10 DIME...

Page 12: ...ion you may require For all spare parts orders or technical support requests send your request to service epg leroy somer com or your closest contact whom you will find at www lrsm co support indicati...

Page 13: ...ith local legislation regarding product disposal and recycling Waste hazardous materials The following components and materials require special treatment and must be separated from the alternator befo...

Page 14: ...2018 01 g 14 Electric Power Generation Installation and maintenance R150 AVRs 5384 en...

Page 15: ...ent repair support and maintenance services Trust your alternator maintenance and support to electric power generation experts Our field personnel are 100 qualified and fully trained to operate in all...

Page 16: ...2018 01 g www leroy somer com epg 5384 en Linkedin com company Leroy Somer Twitter com Leroy_Somer_en Facebook com LeroySomer Nidec en YouTube com LeroySomerOfficiel...

Reviews: