19.46
: Analog input AI5 level
Adjustment range : ±100.00 %
Format
: 16-bit
Indicates as a percentage the signal level on
the analog input.
19.47
: Analog input 5 filter
Adjustment range : None (0), 4 ms (1), 8 ms (2),
16 ms (3), 32 ms (4).
Factory setting
: 8 ms (2)
Format
: 8-bit
None (0):
No filtering is applied to analog input AI5.
4 ms (1) to 32 ms (4):
Used to set the filter time constant applied to
analog input AI5.
19.48
: AI5 signal type
Adjustment range : 0-20 mA (0), 20-0 mA (1),
4-20 mA with detection (2),
20-4 mA with detection (3),
4-20 mA without detection
(4), 20-4 mA without
detection (5), 0-10V (6),
+/- 10V (7)
Factory setting
: 0-10V (6)
Format
: 8-bit
Used to define the type of signal connected to
the differential analog input AI5.
19.49
: AI5 current loop
Adjustment range : Active (0) or Lost (1)
Format
: 8-bit
In 4-20 mA current mode with or without
detection, this parameter changes to “1” when
the analog signal drops below 3 mA.
19.50
: Analog input AI5 scaling
Adjustment range : 0 to 2.50
Factory setting
: 1.00
Format
: 16-bit
Used to supply the destination parameter
with a numerical value in proportion with the
input. However, in the majority of cases, this
setting is not necessary since the input is
automatically scaled, meaning that 100% as
an input corresponds to the maximum value
of the destination parameter selected in
19.52.
19.51
: Analog input AI5 inversion
Adjustment range : No (0) or Yes (1)
Factory setting
: No (0)
Format
: 8-bit
Used to invert the input signal.
No (0):
Input signal not inverted.
Yes (1):
Input signal inverted.