C200/C300 Step By Step Guide
5
Issue Number: 1
English
F
D
Ita
E
STEP 4: Select supply / motor cables and fuses or MCB
The supply/motor cables and fuses or MCB’s used should follow he ratings provided in the table below:
* These fuses are fast acting.
** For UL installations, the circuit breaker must be listed under category control number DIVQ / DIVQ7, rated
600 Vac with a short circuit rating > 10 kA. In other countries, circuit breakers compliant with EN IEC 60947-2 are
recommended, with > 10 kA short circuit breaking capacity
The voltage rating of fuses and MCBs must be greater than or equal to the highest supply voltage of
the system.
Fuses
: The AC supply to the drive must be installed wi h suitable protection against
overload. Failure to observe this requirement will cause risk of fire.
Ground conductor size:- Either 10 mm² or two conductors of the same cross-sectional area as the input
conductors.
Model
Input
Phases
Fuses
MCB
rating**
Cables
IEC Class
gG
UL
Class CC
J, or T
*
IEC60364-5-52
mm²
UL 508C
AWG
A
A
Input
Output
Input
Output
01100017
1
10
15
15
1
1
16
16
01100024
1
16
15
15
1.5
1
14
16
02100042
1
20
20
15
2.5
1
12
16
02100056
1
25
25
15
4
1
10
16
01200017
1
6
6
15
1
1
16
16
01200024
1
6
6
15
1
1
16
16
01200033
1
10
15
15
1
1
16
16
01200042
1
16
15
15
1
1
16
16
02200024
1 / 3
6/6
6/6
15
1
1
16
16
02200033
1 / 3
10/10
10/10
15
1
1
16
16
02200042
1 / 3
16/10
15/10
15
1
1
16
16
02200056
1 / 3
20/16
20/15
15
2.5/1.5
1
12/14
16
02200075
1 / 3
20/16
20/15
15
2.5
1
12
16
03200100
1 / 3
25/20
25/20
25/20
4
1.5
10/12
14
04200133
1 / 3
25/20
25/20
25/20
4/2.5
2.5
10
12
04200176
3
25
25
25
4
2.5
10
12
02400013
3
6
6
15
1
1
16
16
02400018
3
6
6
15
1
1
16
16
02400023
3
6
6
15
1
1
16
16
02400032
3
6
6
15
1
1
16
16
02400041
3
10
6
15
1
1
16
16
03400056
3
10
15
15
1
1
14
16
03400073
3
16
15
15
1.5
1
12
16
03400094
3
16
15
25
2.5
1.5
12
14
04400135
3
20
20
20
2.5
2.5
10
12
04400170
3
25
25
25
4
2.5
10
12
The product is UL listed for use on a circuit up to 100 kA maximum supply symmetrical fault current,
when protected by fuses.
IEC cable sizes assume Copper conductor, PVC insulation, Installation method B2 and ambient
temperature of 40 °C (104 °F). UL cable sizes assume Copper conductor with insulation rated at 75 °C
(167 °F).
WARNING
NOTE
NOTE
NOTE