STEP 4:  Select supply / motor cables and fuses or MCB

The supply/motor cables and fuses or MCB’s used should follow  he ratings provided in the table below:

* These fuses are fast acting.
** For UL installations, the circuit breaker must be listed under category control number DIVQ / DIVQ7, rated 
600 Vac with a short circuit rating > 10 kA. In other countries, circuit breakers compliant with EN IEC 60947-2 are 
recommended, with > 10 kA short circuit breaking capacity

The voltage rating of fuses and MCBs must be greater than or equal to the highest supply voltage of 
the system. 

Fuses

: The AC supply to the drive must be installed wi h suitable protection against 

overload. Failure to observe this requirement will cause risk of fire.

Ground conductor size:- Either 10 mm² or two conductors of the same cross-sectional area as the input 
conductors.

Model

Input 

Phases

Fuses

MCB 

rating**

Cables

IEC Class 

gG

UL

Class CC 

J, or T

*

 

IEC60364-5-52

mm²

UL 508C

AWG

A

A

Input

Output

Input

Output

01100017

1

10

15

15

1

1

16

16

01100024

1

16

15

15

1.5

1

14

16

02100042

1

20

20

15

2.5

1

12

16

02100056

1

25

25

15

4

1

10

16

01200017

1

6

6

15

1

1

16

16

01200024

1

6

6

15

1

1

16

16

01200033

1

10

15

15

1

1

16

16

01200042

1

16

15

15

1

1

16

16

02200024

1 / 3

6/6

6/6

15

1

1

16

16

02200033

1 / 3

10/10

10/10

15

1

1

16

16

02200042

1 / 3

16/10

15/10

15

1

1

16

16

02200056

1 / 3

20/16

20/15

15

2.5/1.5

1

12/14

16

02200075

1 / 3

20/16

20/15

15

2.5

1

12

16

03200100

1 / 3

25/20

25/20

25/20

4

1.5

10/12

14

04200133

1 / 3

25/20

25/20

25/20

4/2.5

2.5

10

12

04200176

3

25

25

25

4

2.5

10

12

02400013

3

6

6

15

1

1

16

16

02400018

3

6

6

15

1

1

16

16

02400023

3

6

6

15

1

1

16

16

02400032

3

6

6

15

1

1

16

16

02400041

3

10

6

15

1

1

16

16

03400056

3

10

15

15

1

1

14

16

03400073

3

16

15

15

1.5

1

12

16

03400094

3

16

15

25

2.5

1.5

12

14

04400135

3

20

20

20

2.5

2.5

10

12

04400170

3

25

25

25

4

2.5

10

12

The product is UL listed for use on a circuit up to 100 kA maximum supply symmetrical fault current, 
when protected by fuses.

IEC cable sizes assume Copper conductor, PVC insulation, Installation method B2 and ambient 
temperature of 40 °C (104 °F). UL cable sizes assume Copper conductor with insulation rated at 75 °C 
(167 °F).

WARNING

NOTE

NOTE

NOTE

Summary of Contents for Commander C200

Page 1: ...Commander C200 C300 Step By Step Guide Guide pas à pas Schritt für Schritt Anleitung Guida dettagliata Guía detallada Frame sizes 1 to 4 Tailles 1 à 4 Baugrößen 1 bis 4 Taglie da 1 a 4 Tamaños 1 a 4 ...

Page 2: ... 4 Features of the drive Figure 1 1 Feature diagram size 2 shown EMC MOV L1 L2 L3 U V W BR 2 1 3 12 10 7 5 11 11 9 8 6 4 13 Key 1 Rating label on side of drive 2 Identification label 3 Relay connections Refer to Figure 6 3 4 Control connections Refer to Figure 6 3 5 Braking terminal 6 Internal EMC filter screw 7 DC bus 8 DC bus 9 Motor connections Refer to Figure 6 1 10 AC supply connections Refer...

Page 3: ...n 5 1 For UL installations the maximum ambient temperature permitted is 50 C 104 F with any specified derating applied Drives can be panel mounted with 0 mm space between them A minimum clearance of 100 mm 3 94 in is required above and below the drive Refer to section 3 4 in the Power Installation Guide for informa ion on derating for reduced clearances x4 KIT BAG CABLE BRACKET SAFETY INFORMATION ...

Page 4: ...all Mounting Overall Overall Diameter 1 143 mm 5 7 in 160 mm 6 3 in 53 mm 2 08 in 75 mm 2 95 in 130 mm 5 1 in 5 mm 0 2 in 0 75 kg 1 65 Ib 2 194 mm 7 63 in 205 mm 8 07 in 55 mm 2 17 in 75 mm 2 95 in 150 mm 5 9 in 5 mm 0 2 in 1 3 kg 3 0 Ib 3 215 mm 8 46 in 226 mm 8 9 in 70 7 mm 2 80 in 90 mm 3 54 in 160 mm 6 3 in 5 mm 0 2 in 1 5 kg 3 3 Ib 4 265 mm 10 43 in 277 mm 10 9 in 86 mm 3 40 in 115 mm 4 5 in ...

Page 5: ...ut Output Input Output 01100017 1 10 15 15 1 1 16 16 01100024 1 16 15 15 1 5 1 14 16 02100042 1 20 20 15 2 5 1 12 16 02100056 1 25 25 15 4 1 10 16 01200017 1 6 6 15 1 1 16 16 01200024 1 6 6 15 1 1 16 16 01200033 1 10 15 15 1 1 16 16 01200042 1 16 15 15 1 1 16 16 02200024 1 3 6 6 6 6 15 1 1 16 16 02200033 1 3 10 10 10 10 15 1 1 16 16 02200042 1 3 16 10 15 10 15 1 1 16 16 02200056 1 3 20 16 20 15 15...

Page 6: ...ttings shown in the table below Table 6 1 Recommended torque settings Connect the supply and motor connections using the cables and fuses or MCB s quoted in the table shown in Step 4 When using a single phase supply he supply should be connected to L1 and L3 Figure 6 1 Power terminal connections Model size Terminal block description Torque settings All Control terminals 0 2 N m 0 15 Ib ft Relay te...

Page 7: ...to 4 ground connections size 2 shown 1 4 x M4 threaded holes for the ground connection busbar Electrochemical corrosion of grounding terminals Ensure hat grounding terminals are protected against corrosion i e as could be caused by condensation The ground loop impedance must conform to he requirements of local safety regulations The drive must be grounded by a connection capable of carrying the pr...

Page 8: ...er to step 5 Refer to section 4 4 in the Control User Guide for information and wiring diagrams for alternative configurations Drive enable 9 10 11 12 Zero frequency Run forward 13 Run reverse 14 Digital I O Analog input 1 Analog input 2 select Digital Input 2 24 V user Digital I O1 Digital input 3 Digital input 4 Digital input 5 41 42 Drive ok Relay 1 1 2 0V Analog I O Analog input 1 7 Analog out...

Page 9: ...meter values STOP RESET the drive in keypad mode It can also be used to reset the drive in terminal mode ESCAPE Is used to exit from the parameter edit view mode rdy START Is used to start the drive in keypad mode To return to Status Mode press button To return to Parameter View Mode press button Press or to select parameter Status Mode To enter Parameter View Mode press button Parameter View Mode...

Page 10: ... while the drive is performing the autotune Wait for the drive to display inh and for the motor to come to a standstill Remove the drive enable and run signal from the drive Ready to run Analog input terminal mode by default Run The drive is now ready to run the motor Close enable C200 or Safe Torque Off C300 and the Run Forward or Run Reverse terminals Increasing and decreasing speed Changing the...

Page 11: ...on Drive output stage The drive is inhibited and cannot be run The Drive Enable signal is not applied to the drive enable terminal or is set to 0 Disabled The drive is ready to run The drive enable is active but the drive inverter is not active because the final drive run is not ac ive Disabled The drive is stopped holding zero speed Enabled Supply loss condition has been detected Enabled The driv...

Page 12: ...e UL Type 12 when installed with the sealing washer and fixing kit provided When installed in a Type 1 or Type 12 enclosure the drives may be operated in a compartment handling conditioned air A 4 Mounting Drives may be surface mounted using the appropriate brackets Drives may be mounted singly or side by side with suitable space between them bookcase mounting A 5 Environment Drives must be instal...

Page 13: ... BRAKING Commander C200 C300 frame sizes 1 to 4 have been evaluated for dynamic braking applications Other drive models have not been evaluated for dynamic braking A 7 Motor overload protection and thermal memory retention The devices incorporate solid state overload protection for the motor load The protection levels are expressed as a percentage of full load current Refer to the Control User Gui...

Reviews: