Nidec Commander C200 Step-By-Step Manual Download Page 10

10

                                                                                                            C200/C300 Step By Step Guide

Issue Number: 1

STEP 8:  Run the motor

This step will provide instruction on how to set-up the basic drive parameters, perform an auto-tune and run the 
motor in analog input terminal mode or keypad mode.

Action

Detail

Power Up

Ensure:

The drive displays: inh (Enable terminal(s) is open)

Minimum and 
maximum speed

Enter:

Minimum speed Pr

01

 (Hz) 

Maximum speed Pr

02

 (Hz)

Accel and Decel 
rates

Enter:

Acceleration rate Pr

03

 (s)

Deceleration rate Pr

04

 (s)

Motor nameplate 
details

Ready to autotune

Autotune

The drive is able to perform either a stationary or a rotating autotune. The motor must be at 
a stands ill before any autotune is enabled and disconnected from the load for a rotating 
autotune.

To perform an autotune:

Set  Pr

10 

to L2.

Go to Pr

38

.

Set  Pr

38 

= 1 for a stationary autotune or set Pr

38

 = 2 for a rotating autotune

Close the drive enable signal (apply +24 V to terminal 11 or terminal 31 and 34 on 
Commander C300). The drive will display ‘rdy’.

Give a Run command (apply +24 V to terminal 12 - Run forward or terminal 13 - 
Run reverse. The display will flash ‘tuning’ while the drive is performing the autotune.

Wait for the drive to display ‘inh’ and for the motor to come to a standstill. 

Remove the drive enable and run signal from the drive.

Ready to run (Analog input terminal mode by default)

Run

The drive is now ready to run the motor. Close enable (C200) or Safe Torque Off (C300) and 
the Run Forward or Run Reverse terminals.

Increasing and 
decreasing speed

Changing the selected Analog frequency reference will increase and decrease the speed of 
the motor.

Stopping

To stop the motor by following  he selected deceleration rate, open either the run forward or 
run reverse terminals. If  he enable terminal is opened while the motor is running, the drive 
output is immediately disabled and the motor will coast to a stop.

Ready to run (Keypad mode)

Run

The drive is now ready to run the motor.  Set Pr

05

 to 'PAd'.  Close enable (C200) or Safe 

Torque Off (C300).

Press the start key 

Increasing and 
decreasing speed

Press the up and down keys 

 to increase and decrease the speed.

Stopping

Press the Stop/Reset key 

Motor rated current in Pr

06

 (Amps)

Motor rated speed in Pr

07

 (rpm / min

-1

)

Motor rated voltage in Pr

08

 (Volts)

Motor Rated Power factor (Cos ) in Pr

09

MOT  3

LS 80 L T

N

734570 BJ 002    kg

9

40 C

S1

IP 55

I cl F

V

Hz min

kW cos

-1

A

230 50 2800 0,75 0,83

0,3

1

2

3

4

Summary of Contents for Commander C200

Page 1: ...Commander C200 C300 Step By Step Guide Guide pas à pas Schritt für Schritt Anleitung Guida dettagliata Guía detallada Frame sizes 1 to 4 Tailles 1 à 4 Baugrößen 1 bis 4 Taglie da 1 a 4 Tamaños 1 a 4 ...

Page 2: ... 4 Features of the drive Figure 1 1 Feature diagram size 2 shown EMC MOV L1 L2 L3 U V W BR 2 1 3 12 10 7 5 11 11 9 8 6 4 13 Key 1 Rating label on side of drive 2 Identification label 3 Relay connections Refer to Figure 6 3 4 Control connections Refer to Figure 6 3 5 Braking terminal 6 Internal EMC filter screw 7 DC bus 8 DC bus 9 Motor connections Refer to Figure 6 1 10 AC supply connections Refer...

Page 3: ...n 5 1 For UL installations the maximum ambient temperature permitted is 50 C 104 F with any specified derating applied Drives can be panel mounted with 0 mm space between them A minimum clearance of 100 mm 3 94 in is required above and below the drive Refer to section 3 4 in the Power Installation Guide for informa ion on derating for reduced clearances x4 KIT BAG CABLE BRACKET SAFETY INFORMATION ...

Page 4: ...all Mounting Overall Overall Diameter 1 143 mm 5 7 in 160 mm 6 3 in 53 mm 2 08 in 75 mm 2 95 in 130 mm 5 1 in 5 mm 0 2 in 0 75 kg 1 65 Ib 2 194 mm 7 63 in 205 mm 8 07 in 55 mm 2 17 in 75 mm 2 95 in 150 mm 5 9 in 5 mm 0 2 in 1 3 kg 3 0 Ib 3 215 mm 8 46 in 226 mm 8 9 in 70 7 mm 2 80 in 90 mm 3 54 in 160 mm 6 3 in 5 mm 0 2 in 1 5 kg 3 3 Ib 4 265 mm 10 43 in 277 mm 10 9 in 86 mm 3 40 in 115 mm 4 5 in ...

Page 5: ...ut Output Input Output 01100017 1 10 15 15 1 1 16 16 01100024 1 16 15 15 1 5 1 14 16 02100042 1 20 20 15 2 5 1 12 16 02100056 1 25 25 15 4 1 10 16 01200017 1 6 6 15 1 1 16 16 01200024 1 6 6 15 1 1 16 16 01200033 1 10 15 15 1 1 16 16 01200042 1 16 15 15 1 1 16 16 02200024 1 3 6 6 6 6 15 1 1 16 16 02200033 1 3 10 10 10 10 15 1 1 16 16 02200042 1 3 16 10 15 10 15 1 1 16 16 02200056 1 3 20 16 20 15 15...

Page 6: ...ttings shown in the table below Table 6 1 Recommended torque settings Connect the supply and motor connections using the cables and fuses or MCB s quoted in the table shown in Step 4 When using a single phase supply he supply should be connected to L1 and L3 Figure 6 1 Power terminal connections Model size Terminal block description Torque settings All Control terminals 0 2 N m 0 15 Ib ft Relay te...

Page 7: ...to 4 ground connections size 2 shown 1 4 x M4 threaded holes for the ground connection busbar Electrochemical corrosion of grounding terminals Ensure hat grounding terminals are protected against corrosion i e as could be caused by condensation The ground loop impedance must conform to he requirements of local safety regulations The drive must be grounded by a connection capable of carrying the pr...

Page 8: ...er to step 5 Refer to section 4 4 in the Control User Guide for information and wiring diagrams for alternative configurations Drive enable 9 10 11 12 Zero frequency Run forward 13 Run reverse 14 Digital I O Analog input 1 Analog input 2 select Digital Input 2 24 V user Digital I O1 Digital input 3 Digital input 4 Digital input 5 41 42 Drive ok Relay 1 1 2 0V Analog I O Analog input 1 7 Analog out...

Page 9: ...meter values STOP RESET the drive in keypad mode It can also be used to reset the drive in terminal mode ESCAPE Is used to exit from the parameter edit view mode rdy START Is used to start the drive in keypad mode To return to Status Mode press button To return to Parameter View Mode press button Press or to select parameter Status Mode To enter Parameter View Mode press button Parameter View Mode...

Page 10: ... while the drive is performing the autotune Wait for the drive to display inh and for the motor to come to a standstill Remove the drive enable and run signal from the drive Ready to run Analog input terminal mode by default Run The drive is now ready to run the motor Close enable C200 or Safe Torque Off C300 and the Run Forward or Run Reverse terminals Increasing and decreasing speed Changing the...

Page 11: ...on Drive output stage The drive is inhibited and cannot be run The Drive Enable signal is not applied to the drive enable terminal or is set to 0 Disabled The drive is ready to run The drive enable is active but the drive inverter is not active because the final drive run is not ac ive Disabled The drive is stopped holding zero speed Enabled Supply loss condition has been detected Enabled The driv...

Page 12: ...e UL Type 12 when installed with the sealing washer and fixing kit provided When installed in a Type 1 or Type 12 enclosure the drives may be operated in a compartment handling conditioned air A 4 Mounting Drives may be surface mounted using the appropriate brackets Drives may be mounted singly or side by side with suitable space between them bookcase mounting A 5 Environment Drives must be instal...

Page 13: ... BRAKING Commander C200 C300 frame sizes 1 to 4 have been evaluated for dynamic braking applications Other drive models have not been evaluated for dynamic braking A 7 Motor overload protection and thermal memory retention The devices incorporate solid state overload protection for the motor load The protection levels are expressed as a percentage of full load current Refer to the Control User Gui...

Reviews: