Technical specifications
-
1x230 V
Output data according to EN 14 511
1.42 / 3.87
1
kW/-
Capacity (P
H
)/COP
1.34 / 3.13
2
kW/-
Capacity (P
H
)/COP
1.27 / 2.65
3
kW/-
Capacity (P
H
)/COP
Electrical data
230 V ~ 50 Hz
V
Rated voltage
3.5
A
Max operating current
6
A
Min. fuse rating
5-20
W
Driving power circulation pump
20-75
W
Driving power fan
IP21
Enclosure class
Refrigerant circuit
R134A
Type of refrigerant
1430
GWP refrigerant
0.38
kg
Volume
0.54
ton
CO
2
equivalent
2.2 / 22.0
MPa/bar
Cut-out value pressostat HP
Exhaust air module
1.0 / 10.0
MPa/bar
Max system pressure
63
°C
Max temperature, supply line
54
°C
Max temperature, return line
Air flow requirement
25
l/s
Min. air flow at exhaust air temperature at least 10°C
10 - 37
°C
Temperature range for compressor operation
Sound effect level according to EN 12 102
47.0
dB(A)
Sound power level (L
W(A)
)
4
Sound pressure levels according to EN ISO 11 203
43.0
dB(A)
Sound pressure level in the installation room (L
P(A)
)
5
Pipe connections
22
mm
Heating medium ext Ø
160
mm
Ventilation ext Ø
160/125
mm
Filter box ext. Ø
1 A20(12)W35, frånluftsflöde 50 l/s (180 m
3
/h), exkl. driveffekt för fläkt
2 A20(12)W45, frånluftsflöde 50 l/s (180 m
3
/h), exkl. driveffekt för fläkt
3 A20(12)W55, frånluftsflöde 50 l/s (180 m
3
/h), exkl. driveffekt för fläkt
4
The value varies with the fan speed selected. For more detailed sound data, including sound to ducts, visit
5
The value can vary with the room’s damping capacity. These values apply at a damping of 4 dB.
Other 1x230 V
Dimensions and weight
600
mm
Width
626
mm
Depth
490 - 515
Height
50
kg
Weight
624 45 25
RSK No.
066 161
Part No.
29
Chapter 10 | Technical data