The circulation pump runs at a fixed speed. Can be
changed in menu 7.2.13.
Caution
As long as the start guide is active, no function
in the installation will start automatically.
The guide will appear at each installation restart
until it is deselected on the last page.
SETTING VENTILATION (EXHAUST AIR)
The ventilation must be set according to applicable
standards. Set the fan speed in menu 7.1.4.1.
Even if ventilation is roughly set at installation it is im-
portant that a ventilation adjustment is ordered and
permitted.
NOTE
Order a ventilation adjustment to complete the
setting.
Fan capacity
0
0
0
50
100
150
200
250
25
50
75
(m
3
/h)
100
200
300
400
500
Tillgängligt tryck
(Pa)
(l/s)
Luftflöde
30%
100%
80%
60%
40%
50%
70%
90%
Available pressure
Airflow
Power, fan
0
0
0
50
100
150
200
250
25
50
75
(m
3
/h)
20
40
60
80
100
Effekt
(w)
(l/s)
Luftflöde
30%
100%
80%
60%
40%
50%
70%
90%
Output
Airflow
23
Chapter 6 | Commissioning and adjusting
NIBE S135