Nibe S135 Installation Manual Download Page 1

IHB EN 1925-1
531281

INSTALLATION MANUAL

Exhaust air module
NIBE S135

Summary of Contents for S135

Page 1: ...IHB EN 1925 1 531281 INSTALLATION MANUAL Exhaust air module NIBE S135 ...

Page 2: ......

Page 3: ...lation exhaust air 17 General ventilation connections 17 Dimension and ventilation connections 18 Ventilation flow exhaust air 18 Adjusting ventilation exhaust air 19 5 Electrical connections 19 General 19 Connections 21 Optional connections 22 6 Commissioning and adjusting 22 Preparations 22 Filling and venting 22 Start up and inspection 24 7 Control Menus 24 Menu system 26 8 Disturbances in comf...

Page 4: ...to make any design or technical modifications are reserved NIBE 2019 Symbols NOTE This symbol indicates danger to person or ma chine Caution This symbol indicates important information about what you should consider when installing or servicing the installation TIP This symbol indicates tips on how to facilitate using the product Marking The CE mark is obligatory for most products sold in the EU r...

Page 5: ... Do not dispose of used products with normal household waste It must be disposed of at a special waste station or dealer who provides this type of service Improper disposal of the product by the user results in administrative penalties in accordance with current le gislation 5 Chapter 1 Important information NIBE S135 ...

Page 6: ... carried out by a suitably qualified person Date Signature Notes Description Ventilation exhaust air page 15 Setting the ventilation flow Exhaust air filter Heating medium page 22 System flushed System vented Circulation pump setting System pressure Electricity page 19 Supply connected 230 V Circuit fuses NIBE S135 Chapter 1 Important information 6 ...

Page 7: ...is is not possible avoid placing it against a wall behind a bed room or other room where noise may be a problem Wherever the unit is located walls to sound sensitive rooms should be fitted with sound insulation Route pipes so they are not fixed to an internal wall that backs on to a bedroom or living room INSTALLATION AREA Leave a free space of 800 mm in front of the product Leave free space betwe...

Page 8: ... 1 Only for VVM 310 VVM 500 LOCATION The kit of supplied items is placed on top of the product Removing the covers FRONT HATCH LEK 1 2 3 4 1 Slacken off the screws for the securing plate above S135 2 Slide the hatch upwards and pull it towards you 3 Pull the hatch towards yourself NOTE An earth cable is installed in the hatch which can therefore only be lifted out 35 cm If the hatch needs to be re...

Page 9: ...S 1 Undo the screws at the edge 2 Twist the cover slightly outward 3 Move the side cover outwards and backwards 4 Assembly takes place in the reverse order LEK LEK LEK 9 Chapter 2 Delivery and handling NIBE S135 ...

Page 10: ...tions LEK LE K L E K BT76 PF1 EB10 X11 GQ10 BT77 BT12 PF3 X10 AA2 QM25 XL44 XL43 BT16 QN20 HZ2 EP2 BP1 BT13 XL9 EP1 GQ1 XL8 CA1 QN1 NIBE S135 Chapter 3 The exhaust air module design 10 3 The exhaust air module design ...

Page 11: ... evaporator BT16 Temperature sensor defrosting BT76 Temperature sensor incoming air BT77 ELECTRICAL COMPONENTS Base card AA2 Capacitor CA1 Compressor heater EB10 PWM switch circulation pump X10 Terminal block communication with indoor module X11 COOLING COMPONENTS Evaporator EP1 Condenser EP2 Compressor GQ10 Drying filter HZ2 Expansion valve QN1 Solenoid valve defrosting QN20 VENTILATION Fan GQ1 A...

Page 12: ...t water pockets and must also be frost proof To make the installation energy efficient NIBE recom mends that all pipes between S135 and the indoor module are insulated The insulation should be at least 12 mm thick NOTE The pipe systems need to be flushed out be fore S135 is connected so that any debris cannot damage component parts COMPATIBLE NIBE PRODUCTS VVM S325 VVM S320 SMO S40 SYMBOL KEY Mean...

Page 13: ...om gas to liquid The refrigerant then goes via filters to the expansion valve where the pressure and temperature are reduced The refrigerant has now completed its circulation and returns to the evaporator XL8 XL9 Heating medium connection supply XL8 Heating medium connection return XL9 Caution This is a principle of operation differences may occur in the installation in question Dimensions and pip...

Page 14: ...ooves on the exhaust air module Ensure that the exhaust air module is installed horizontally INSTALLING BRACKETS 1 Install the brackets together using the M6 screws and nuts supplied 567 425 2 Drill holes in the wall as illustrated 567 425 3 Mount the brackets on the wall 4 Screw S135 into place in the brackets using the M5 screws and nuts supplied LEK LEK NIBE S135 Chapter 4 Pipe and air connecti...

Page 15: ...rding to the instructions in this manual Installation must be carried out in accordance with cur rent standards and directives EXHAUST AIR Connecting the exhaust air The heat pump uses the heat that is in the building s ventilation air to heat the building and the hot water at the same time that the house is ventilated The hot air is transferred from the rooms to the heat pump via the exhaust air ...

Page 16: ... pipe cooling In these cases 4 pipe cooling must be connected between the air water heat pump and S135 Where there is also a pool S135 must be connected between 4 pipe cooling and pool S135 can produce hot water at the same time as the air water heat pump is producing cooling A shut off valve QN44 is required for this The demand on S135 is controlled by the indoor module in the system The pump and...

Page 17: ...h the enclosed air filter EXHAUST AIR DUCT KITCHEN FAN Exhaust air duct kitchen fan must not be connected to S135 To prevent food vapour being transferred to S135 the distance between the kitchen fan and the exhaust air device must be considered The distance should not be less than 1 5 m but this can vary between different in stallations Always use a kitchen fan when cooking INSTALL THE FILTER CAR...

Page 18: ...required The ventilation capacity is set in the indoor module s menu system menu 7 1 4 1 Adjusting ventilation exhaust air To obtain the necessary air exchange in every room of the house the exhaust air devices must be correctly positioned and adjusted and the fan in the exhaust air module adjusted Immediately after installation adjust the ventilation so that it is set according to the projected v...

Page 19: ...l the boiler has been filled Internal components can be damaged NOTE Electrical installation and service must be car ried out under the supervision of a qualified electrician Electrical installation and wiring must be carried out in accordance with the stipulations in force Connections POWER CONNECTION NOTE To prevent interference unscreened commu nication and or sensor cables to external con nect...

Page 20: ...0 1 X11 2 AA2 X30 3 X11 1 AA2 X30 4 LEK 2 3 1 X11 NOTE Cable between the indoor module and S135 must be a max of 15 m AA2 X30 B A GND 12V 2 3 4 1 AA2 XF11 A GND B 2 3 4 1 VVM S S135 CONTROL MODULE Connect the control module s joint board AA100 X9 to the supplied 4 pin connector X11 according to the table Connect the connector X11 to XF11 Use a 3 core cable of at least 0 5 mm cable area Contact Ind...

Page 21: ...he connector X10 to XF10 and connect the cable to the circulation pump 1 2 3 4 5 6 Blue Black Brown S135 XF10 Optional connections Connecting the shut off valve QN44 Connect the shut off valve s motor QN44 to AA5 X9 2 signal AA5 X9 1 N and AA5 X10 2 230 V in the cooling accessory s unit box X10 1 2 3 4 5 6 7 8 9 Unit box External AA5 X9 AA5 X10 QN44 Black Blue Brown 21 Chapter 5 Electrical connect...

Page 22: ...st air module 2 Vent the exhaust air module via the vent valve QM25 and the rest of the climate system via the relevant vent valves 3 Keep topping up and venting until all air has been removed and the pressure is correct QM25 Start up and inspection START UP WITH NIBE INDOOR MODULE NOTE There must be water in the climate system before S135 is started NOTE The circulation pump must not be powered u...

Page 23: ...ds Set the fan speed in menu 7 1 4 1 Even if ventilation is roughly set at installation it is im portant that a ventilation adjustment is ordered and permitted NOTE Order a ventilation adjustment to complete the setting Fan capacity 0 0 0 50 100 150 200 250 25 50 75 m3 h 100 200 300 400 500 Tillgängligt tryck Pa l s Luftflöde 30 100 80 60 40 50 70 90 Available pressure Airflow Power fan 0 0 0 50 1...

Page 24: ...ntilation If the temperature difference is greater than the set value for Min diff outdoor and exhaust air and the exhaust air temperature is higher than the set value for Start temperature exhaust air the ventilation operates at speed 4 until one of these conditions is no longer valid Caution Night cooling is only activated when heating is not permitted MENU 1 2 5 FAN RETURN TIME Select the retur...

Page 25: ...d in Menu 7 3 2 1 heat pump to allow hot water during cooling to be activated MENU 7 1 4 1 FAN SPEED EXHAUST AIR Normal and Speed 1 4 Setting range 0 100 Set the speed for the five different selectable speeds for the fan here 25 Chapter 7 Control Menus NIBE S135 ...

Page 26: ...usted Order implement ventilation adjustment Exhaust air device blocked or throttled down too much Check and clean the exhaust air devices Fan speed in reduced mode Enter menu 1 2 1 and select normal LOUD OR DISTURBING VENTILATION EXHAUST AIR INSTALLATION Filter HQ12 blocked Clean or replace the filter The ventilation is not adjusted Order implement ventilation adjustment Fan speed in forced mode ...

Page 27: ...ible with S135 For more information see the Installer Manual for the relevant accessory Top cabinet TOC 40 Top cabinet which conceals any pipes ventilation ducts HEIGHT 345 MM Part no 089 757 RSK no 625 06 88 HEIGHT 245 MM Part no 089 756 RSK no 625 06 87 HEIGHT 385 635 MM Part no 089 758 RSK no 625 06 89 HEIGHT 445 MM Part no 067 522 RSK no 625 12 99 27 Chapter 9 Accessories NIBE S135 9 Accessori...

Page 28: ...Dimensions and setting out coordinates 370 626 220 155 440 595 210 Ø160 Ø125 40 420 65 90 420 NIBE S135 Chapter 10 Technical data 28 10 Technical data ...

Page 29: ...rature range for compressor operation Sound effect level according to EN 12 102 47 0 dB A Sound power level LW A 4 Sound pressure levels according to EN ISO 11 203 43 0 dB A Sound pressure level in the installation room LP A 5 Pipe connections 22 mm Heating medium ext Ø 160 mm Ventilation ext Ø 160 125 mm Filter box ext Ø 1 A20 12 W35 frånluftsflöde 50 l s 180 m3 h exkl driveffekt för fläkt 2 A20 ...

Page 30: ... heating energy efficiency average climate 47 dB Sound power level LWA indoors 2 kW Rated heat output Pdesignh cold climate 2 kW Rated heat output Pdesignh warm climate 1004 1264 kWh Annual energy consumption space heating cold cli mate 587 731 kWh Annual energy consumption space heating warm cli mate 147 117 Seasonal space heating energy efficiency cold climate 136 110 Seasonal space heating ener...

Page 31: ...OPd Tj biv kW 1 2 Pdh Tj biv 2 8 COPd Tj TOL kW 1 2 Pdh Tj TOL COPd Tj 15 C if TOL 20 C kW Pdh Tj 15 C if TOL 20 C C 10 TOL Min outdoor air temperature C 6 9 Tbiv Bivalent temperature COPcyc Cycling interval efficiency kW Pcych Cycling interval capacity C 58 WTOL Max supply temperature 0 98 Cdh Degradation coefficient Additional heat Power consumption in modes other than active mode kW 0 3 Psup Ra...

Page 32: ...AM Part Specification Sheet 051133 5 Page 2 2 Created 2019 03 20 07 56 0 001 GBN 2019 03 20 Production GBN 2014 12 03 230V 50Hz WIR DIAGRAM NIBE F135 S135 ELSCHEMA NIBE F135 S135 051133 5 NIBE S135 Chapter 10 Technical data 32 ...

Page 33: ...n of the installation 6 Installation area 7 M Marking 4 Mounting Installation Suspension 14 P Pipe and air connections 12 Pipe and ventilation connections Connecting the climate system 15 Dimensions and pipe connections 13 15 Exhaust air duct 17 General pipe connections 12 Pipe dimensions 13 Symbol key 12 System diagram 13 Pipe dimensions 13 Possible selection for AUX inputs 21 Preparations 22 R R...

Page 34: ......

Page 35: ... NORWAY NETHERLANDS GREAT BRITAIN ABK AS Brobekkveien 80 0582 Oslo Tel 47 23 17 05 20 post abkklima no nibe no NIBE Energietechniek B V Energieweg 31 4906 CG Oosterhout Tel 31 0 168 47 77 22 info nibenl nl nibenl nl NIBE Energy Systems Ltd 3C Broom Business Park Bridge Way S41 9QG Chesterfield Tel 44 0 845 095 1200 info nibe co uk nibe co uk SWEDEN RUSSIA POLAND NIBE Energy Systems Box 14 Hannabad...

Page 36: ...IBE Energy Systems All product illustrations facts and data are based on the available information at the time of the publication s approval NIBE Energy Systems makes reservations for any factual or printing errors in this manual 2019 NIBE ENERGY SYSTEMS 531281 WS name Gemensamt WS version a666 WS release date 2019 06 26 07 52 Publish date 2019 07 04 09 20 ...