Transport and storage

HBS 05 should be transported and stored vertically in a
dry place.

NOTE

Ensure that the heat pump cannot fall over
during transport.

Assembly

It is recommended that HBS 05 is installed in a room
with existing floor drainage, most suitably in a utility
room or boiler room.

The brackets for HBS 05 are screwed to the wall using
the enclosed screws. Mounting template enclosed.

Route pipes so they are not fixed to an internal wall
that backs on to a bedroom or living room.

Ensure that there is approx. 800 mm free space in front
of and 400 mm above the product for any future ser-
vice. Ensure that there is sufficient space above the
machine for pipework and valves.

Caution

HBS 05 will end up approx. 10 mm out from
the wall when it has been mounted on the
brackets.

NOTE

Condensation hose (WP3) must be connected
to holes in the underside of HBS 05.

Mounting the SPLIT box HBS 05

LEK

2

1

LEK

3

1. Position the enclosed mounting template horizontally
against the wall. (See the dimensions on the mounting
template.) Mark for drilling holes.

LEK

2

1

LEK

3

2. Screw the brackets to the wall using the enclosed
screws.

UN

3. Install HBS 05 on the brackets. Finally, install the cover.

9

Chapter 2 |

Delivery and handling

HBS 05

2 Delivery and handling

Summary of Contents for HBS 05 Series

Page 1: ...Installer manual LEK HBS 05 HBS 05 6 05 12 05 16 SPLIT box IHB EN 1746 1 331901...

Page 2: ......

Page 3: ...s 19 Pipe coupling heating medium circuit 19 Pressure drop heating medium side 19 Docking alternatives 22 5 Electrical connections 22 General 24 Electrical components 24 Accessibility electrical conne...

Page 4: ...t the measurement values If the refri gerant concentration exceeds the limit there may be a shortage of oxygen in the event of any leak which can cause serious injury Use original accessories and the...

Page 5: ...powder or other powder that can enter the air Locations where substances that can affect the unit for example sulphide gas chlorine acid or alkaline substances can occur Locations with direct exposur...

Page 6: ...te stations Do not dispose of used products with normal household waste It must be disposed of at a special waste station or dealer who provides this type of service Improper disposal of the product b...

Page 7: ...off and drain valve Charge flow set Electricity page 22 Fuses property Safety breaker Earth circuit breaker Heating cable type effect Fuse size heating cable F3 Communication cable connected AMS 10 ad...

Page 8: ...t difference Pressurization test Leak testing End pressure vacuum Pipe insulation Checked Notes Electrical installation Property s main fuse Group fuse Current limiter current sensor KVR 10 Checked No...

Page 9: ...800 mm free space in front of and 400 mm above the product for any future ser vice Ensure that there is sufficient space above the machine for pipework and valves Caution HBS 05 will end up approx 10...

Page 10: ...e space in front of HBS 05 Recommendation for positioning on wall LEK Placering v gg Min 30 cm Min 20 cm Min 20 cm Recommendation for positioning on wall in corner LEK LEK Placering v gg h rn Placerin...

Page 11: ...Removing the covers HBS 05 LEK LEK LEK LEK 11 Chapter 2 Delivery and handling HBS 05...

Page 12: ...ation HBS 05 EZ102 UN UN AA23 AA23 X100 X1 AA23 X1 A23 F3 BT15 BP4 BT3 XL53 XL52 XL1 XL2 UB3 UB1 UB2 BT12 EP2 HZ2 PF1 PF3 AA23 X4 WP3 AA23 S3 PF4 PF3 HBS 05 Chapter 3 The heat pump design 12 3 The hea...

Page 13: ...Terminal block communication with in door module control module AA23 X4 Terminal block communication outdoor module AMS 10 AA23 X100 Terminal block incoming supply X1 Sensor thermostats Pressure sens...

Page 14: ...heating cable AA23 F3 DIP switch addressing of outdoor unit AA23 S3 Terminal block incoming supply connec tion of KVR AA23 X1 Terminal block communication with in door module control module AA23 X4 T...

Page 15: ...8 C HBS 05 is not equipped with shut off valves on the water side these must be installed to facilitate any future ser vicing When docking with HBS 05 free flow in the climate sys tem is recommended f...

Page 16: ...S 10 Pipe dimensions and materials AMS 10 6 Liquid pipe Gas pipe 6 35 mm 1 4 12 7 mm 1 2 Pipe dimension Flare 1 4 Flare 1 2 Connection Copper quality SS EN 12735 1 or C1220T JIS H3300 Material 0 8 mm...

Page 17: ...ding tool Connect the flare connector and tighten to the follow ing torque Use the Tightening angle if a torque wrench is not available Recommen ded tool length mm Tightening angle Tightening torque N...

Page 18: ...fol lowed The connection lines must be as large and short as possible Evacuate the system down to 4 mbar and fill the system with dry nitrogen to atmospheric pressure to the finish the evacuation Fill...

Page 19: ...nt regulations for all docking options To ensure fault free operation of the system it is recommen ded to give consideration to the values according to the table when adjusting the system See www nibe...

Page 20: ...ff valve Non return valve Control valve Safety valve Temperature sensor Expansion vessel Pressure gauge P Circulation pump Shunt shuttle valve Fan Domestic hot water Radiator system Under floor heatin...

Page 21: ...ium return BT3 Temperature sensor condenser supply BT12 Temperature sensor fluid pipe BT15 Outdoor module AMS 10 EZ101 SPLIT box HBS 05 EZ102 Safety valve heat pump FL10 Shut off valve QM41 Filterball...

Page 22: ...s will be loaded with a number of amperes A during compressor operation Check the maximum load in the table below Maximum current A Outdoor module 15 AMS 10 6 16 AMS 10 8 23 AMS 10 12 25 AMS 10 16 Max...

Page 23: ...nstallation L PEN 1 L2 L3 Electrical distribution unit Isolator switch Incoming supply Communication cable HBS 05 AMS 10 Power cable Current sensor NIBE VVM Only in a 3 phase installation 23 Chapter 5...

Page 24: ...weentheunitsmustbeconnectedbetween terminal block AA23 X100 1 X100 2 in HBS 05 and ter minal block TB 2 and TB 3 in AMS 10 Recommendation screened 2 core cable Connect phase brown neutral blue and gro...

Page 25: ...software version Please ensure that the indoor module in this case has at least software version v8320 Connection between HBS 05 and VVM EZ101 BT12 BT3 BT15 BP4 EB101 FL10 QM41 XL52 XL53 XL1 XL2 EZ10...

Page 26: ...nnectedbetween terminal block for communication AA23 X4 1 2 3 in HBS 05 and terminal block for communication X2 19 A 20 B 21 GND in SMO 20 Stripped length of conductor is 6 mm LEK L N 1 1 0 2 3 4 PE 2...

Page 27: ...16 17 18 19 10 11 12 13 14 5 6 7 8 9 1 1 N L PE PE 1 2 3 4 5 6 7 8 2 1 2 3 4 5 6 7 8 9 2 3 4 X8 X4 X10 X1 AA5 X4 SMO 40 and more HBS 05 HBS 05 one or more can communicate with the control module SMO 4...

Page 28: ...cable AA23 F3 NOTE The pipe must be able to withstand the heat from the heating cable To ensure this function the accessory KVR 10 should be used See instructions in the Installer Manual for KVR 10 Ad...

Page 29: ...The communication cable on the terminal block AA23 X4 must not be connected 3 Turn the isolator switch on 4 Ensure that the AMS 10 is connected to the power source 5 After 6 8 hours the communication...

Page 30: ...the system is stable correct pressure and all air eliminated the automatic heating control system can be set as re quired Adjustment charge flow Instructions for adjusting hot water charging can be fo...

Page 31: ...is to be activ ated for the heat pump here During active function you can limit the value of the maximum current Setting range 6 32 A Factory setting 32 A Stop temperature compressor Here you can lim...

Page 32: ...ain fuses of the accommodation The property s earth circuit breaker Check the indoor module or control module See sec tion Disturbances in comfort in the Installer Manual for the indoor module or cont...

Page 33: ...pressure BP4 Condenser EP2 Fan GQ1 FM01 Fan GQ2 FM02 Compressor GQ10 CM Drying filter HS1 Expansion valve heating QN1 EEV H 4 way valve QN2 20S Expansion valve cooling QN3 EEV C Temperature sensor ho...

Page 34: ...LIT BOX HBS 05 16 BP2 BP2 BP1 BP1 BE1 BE1 QN2 QN2 GQ1 GQ2 GQ1 GQ10 GQ10 Outdoor moduleAMS 10 8 AMS 10 12 Outdoor moduleAMS 10 16 Incoming supply Incoming supply QN1 QN3 EEV C EEV H QN1 QN3 EEV H EEV C...

Page 35: ...atur C Tho A R Resistor Temperature C Data for sensor in AMS 10 8 12 16 Tho D Motst nd k Temperatur C Tho D 0 20 40 60 80 100 120 140 160 180 200 0 20 40 60 80 100 120 140 160 Resistor Temperature C T...

Page 36: ...105 74 32 15 3 047 56 20 10 2 976 42 89 5 2 889 33 02 0 2 789 25 61 5 2 673 20 02 10 2 541 15 77 15 2 399 12 51 20 2 245 10 00 25 2 083 8 045 30 1 916 6 514 35 1 752 5 306 40 1 587 4 348 45 1 426 3 58...

Page 37: ...he heat pump runs the de frosting procedure Not an alarm but an operating status Defrosting in progress 183 Insufficient air circulation or blocked heat exchanger Open circuit or short circuit on inpu...

Page 38: ...tes con tinuously High temperature in heat exchanger 261 Can occur when 15V power supply to the inverter PCB is unstable When IPM Intelligent power module displays FO signal Fault Output five times du...

Page 39: ...not work see section Dis turbances in comfort Defective control board in AMS 10 Sensor fault hot gas in AMS 10 Tho D Sensor fault Tho D 279 Open circuit or short circuit on sensor input Sensor does n...

Page 40: ...067 224 SMO 40 Control module Part no 067 225 Indoor module VVM 310 Part no 069 430 VVM 310 With integrated EMK 310 Part no 069 084 VVM320 Copper 3x400 V Part no 069 108 Stainless steel 3x400 V Part...

Page 41: ...L53 XL52 View from above Climate system flow 28 mm XL1 Climate system return 28 mm XL2 Gas line refrigerant HBS 05 12 16 flare 5 8 HBS 05 6 1 2 XL52 Liquid line refrigerant HBS 05 12 16 flare 3 8 HBS...

Page 42: ...erature flow line only compressor 55 C Max temperature return line 25 C Min temperature flow line during heating with compressor and continu ous operation 25 C Maximum temperature supply during coolin...

Page 43: ...on 0 32 0 79 0 20 0 57 0 15 0 38 0 11 0 29 l s Min maxsystemflow coolingoper ation 0 39 0 29 0 19 0 19 l s Min flow climate system 100 circulation pump speed defrosting flow 4 l 5 3 l 5 1 2 5 litre Vo...

Page 44: ...Electrical circuit diagram HBS 05 0 001 LSH 2017 02 21 Production ASN 2015 09 03 230V 230V 2 50Hz WIRING DIAGRAM HBS 05 6 12 16 ELSCHEMA HBS 05 6 12 16 051137 3 HBS 05 Chapter 11 Technical data 44...

Page 45: ...r FM01 FM02 Intelligent power module IPM Induction coil L L1 Indication lamp red LED1 Indication lamp green LED2 Low pressure transmitter LPT Expansion valve for heating QN1 EEV H Expansion valve for...

Page 46: ...8 Electrical components 24 External heating cable KVR 10 28 General 22 Electrical panel 14 Explanation 21 External heating cable KVR 10 28 G General 15 22 H HBS 05 does not communicate 32 HBS 05 is no...

Page 47: ...imate system 29 Topping up the refrigerant 18 Transport and storage 9 Troubleshooting 32 Basic actions 32 HBS 05 does not communicate 32 HBS 05 is not operational 32 High room temperature 32 Large amo...

Page 48: ......

Page 49: ......

Page 50: ......

Page 51: ...ustrielle RD 28 Rue du Pou du Ciel 01600 Reyrieux Tel 04 74 00 92 92 E mail info nibe fr www nibe fr FR NIBE Energy Systems Ltd 3C Broom Business Park Bridge Way S419QG Chesterfield Tel 44 0 845 095 1...

Page 52: ...WS name Gemensamt WS version a423 WS release date 2017 09 25 11 38 Publish date 2017 11 27 08 02 NIBE AB Sweden Hannabadsv gen 5 Box 14 SE 285 21 Markaryd info nibe se www nibe eu 331901...

Reviews: