Control (also with accessories)
13
For the Installer
FIGHTER 1310 HPAC
Gm
[P]
Actual value for number of degree-minutes.
This value can be changed to speed up the start
of heating production.
Setting range: +100/-350.
10
Settings on the display
HP-°min A
[P]
Actual value for number of degree-minutes.
Start value for compressor A.
Setting range: +100/-350.
Default setting is 60.
Deficit before HP module A may start.
HP-°min B
[P]
Actual value for number of degree-minutes.
Start value for compressor B.
Setting range 5 - 250
Default setting is 200.
Deficit before HP module B is allowed to start.
10b
HP-°min A
[P]
Actual value for number of degree-minutes.
Start value for compressor A.
Setting range: +100/-350.
Deficit before HP module A may start.
HP-stop B
[P]
Stop value for compressor B.
Setting range 5 - 250.
Default setting is 150.
Surplus before HP module B may start.
10c
WW diff HP
[P]
Greatest temperature deviation from nominal
value for heating medium (WW) before forced
control of the two heat pump modules A and B
starts.
Setting range: 3 – 25.
Default setting is 13.
Diff AC
Temperature deviation before forced control of
active cooling.
Setting range 1 - 9
Default setting is 4.
11
GM 0
HP-
°
min A 60
HP-
°
min B 200
HP-
°
min A 60
HP-stop B 150
WW diff HP 13
°
C
Diff AC 4
°
C