General points for the installation engineer

11

For the Installer

FIGHTER 1310 HPAC

In accordance with current norms, the heating/cooling
installation must undergo an installation check before
being used. The inspection must be carried out by a
suitably qualified person and should be documented.
The above applies to closed heating/cooling installa-
tions.  If the heat pump or the cooling module are
replaced the installation must be inspected again.

The FIGHTER 1310 must be installed on a firm sur-
face, preferably a concrete floor or a concrete founda-
tion in a boiler room or a separate equipment room.
HPAC is installed suspended on the wall.  Avoid
installing it in or adjacent to a sound-sensitive room.
Wherever the unit is located, any wall that backs on to
a bedroom should be fitted with sound insulation.

The FIGHTER 1310 must be transported and stored
upright and dry. HPAC should be transported and
stored horizontal and dry.

Transport and storage

Setting up the heat pump

Collectors

Inspection of the installation

The length of the collector hose varies depending on
the rock /ground conditions and on the distribution
system. 

The maximum length of each loop is 500 metres.

The hose normally used is PEM hose 40 x 2.4 PN 6.3.

Collectors are always connected in parallel, with some
means of adjusting the flow.

Control of the heating/cooling production normal takes
place according to the floating regulation principle, i.e.
the temperature level needed for cooling/heating at a
specific outdoor temperature is produced with the help
of collected values from the outside and flow sensors.
As an option, room sensors can also be used to com-
pensate for deviations in room temperature.

Floating regulation

PLEASE NOTE! 

This system solution means that the

heat transfer fluid will also circulate

through the heating system. Check

that all component parts are designed

for the heat transfer fluid in question.

Summary of Contents for FIGHTER1310 HPAC

Page 1: ...R INSTALLATION AND MAINTENANCE INSTRUCTIONS FIGHTER1310 HPAC MOS GB 0322 1 611682 FIGHTER1310 HPAC LEK LEK...

Page 2: ......

Page 3: ...26 Setting of heating cooling automatic system Setting of heating cooling 27 Heating curve offset 2 27 Heating curve offset 0 27 Heating curve offset 2 27 Component placement Component placement FIGHT...

Page 4: ..._ Installation engineers Type designation serial number FIGHTER 1310 _ _ kW 089 _ _ _ _ _ _ _ _ _ _ _ Completed by the installation engineer when the heat pump is installed The type of heat transfer f...

Page 5: ...cooling The heat exchange from the heat source rock ground or lake takes place via a closed cooling medi um system where water mixed with antifreeze circu lates to the heat pump Ground water can also...

Page 6: ...Front panel FIGHTER 1310 HPAC For the System manager 4 Indicator lamps Function keys Display Front panel B Switch A D Increase reduce heat C E PLEASE NOTE Make sure there is water in the heat pump be...

Page 7: ...com pressors are running Hot water accessory A steady light shows that hot water charging is in progress Supplementary heating external No function Alarms Flashes rapidly when a fault has occurred Inc...

Page 8: ...supply fan coil units must be To ensure sufficient cooling is obtained the outgoing tem perature to the fan coil units is lowered with a cooling requirement In FIGHTER 1310 HPAC this adaptation is han...

Page 9: ...Using the circulation pumps in FIGHTER 1310 fluid from the ground rock collector circulates through the building s distribution system and cools the building Cooling comes from the ground rock collec...

Page 10: ...s stated on the top row 1 Outdoor Actual outside temperature Room Actual room temperature P Target value set on room sensor Setting range 5 30 C Default setting is 20 C 2 Outdoor Actual outside temper...

Page 11: ...efault setting is 9 Curve C Setting range 1 3 Default setting is 2 6 6b This menu is a submenu to menu 6 and is acti vated by placing the cursor under the value for Curve or Room comp if a room sensor...

Page 12: ...B 7 HP time A Shows the total number running hours for heat pump module A HP time B Shows the total number of running hours for heat pump module B English P Chosen language setting Press Increase to c...

Page 13: ...stored upright and dry HPAC should be transported and stored horizontal and dry Transport and storage Setting up the heat pump Collectors Inspection of the installation The length of the collector hos...

Page 14: ...ow temperature in the form of degree minutes If for example the flow temperature has been 2 degrees lower than the calculated flow temperature for 10 minutes 2 x 10 20 degree minutes is registered by...

Page 15: ...ng is 200 Deficit before HP module B is allowed to start 10b HP min A P Actual value for number of degree minutes Start value for compressor A Setting range 100 350 Deficit before HP module A may star...

Page 16: ...status of high pressure pressure switch es motor protection 1 closed 0 a pressure switch contact is open automatic return Gives a permanent alarm Manual resetting of the motor protection LP Shows the...

Page 17: ...ncrease Reduce heat potentiometer to displace heating curve parallel offset 16 Settings on the display Only shown if the accessory hot water control is installed Cooling P Cooling allowed or not allow...

Page 18: ...Pipe installation must be carried out in accordance with current norms and directives FIGHTER 1310 HPAC can only work up to a return temperature of around 50 C and a flow temperature from the heat pu...

Page 19: ...me Larm Kontrollera att vatten finns i pan nan innan 1 R 0 P B P FIGHTER 1310 HPAC AB B A VXV Berg Jordkollektor FG RG VPA Outline diagram For outline diagrams the necessary safety equipment must be f...

Page 20: ...diagram collector side Available pressure setup A 60 Hz mains supply does not permit the heating medium pump to run at the highest capacity upper curve in the diagrams A frequency converter is needed...

Page 21: ...lectrician If an automatic fuse unit is used this should have a motor characteristic D compressor operation For fuse size see Technical Specifications The FIGHTER 1310 does not include an isolator swi...

Page 22: ...re sensors supplied with the unit FIGHTER 1310 The outside sensor 15 must be installed in a shaded location on a wall facing north or north west where it will not be affected by any morning sun The se...

Page 23: ...ened by loosening the screws at the edges and by the electrical connec tion Check that the valves are set in the required posi tion See the section Electrical connection Valve connections Connect the...

Page 24: ...n switching on the installation and in the operating mode in question 129 130 131 132 NORDICOLD 3V MODULO NORDICOLD 3V MODULO NORDICOLD 3V MODULO NORDICOLD 3V MODULO NORDICOLD 3V MODULO NORDICOLD 3V M...

Page 25: ...HPAC If the valve motors have become loose and the valves have come out of position proceed as set out below to obtain the right valve setting NORDICOLD 3V MODULO The centre punch mark indicates in w...

Page 26: ...PCX ACX PASSIVE ACTIVE COOLING Outgoing voltage 230 V Terminal blocks for external units FIGHTER 1310 Connecting FIGHTER 1310 HPAC Reversing valve RV Electrical connection of the reversing valve for h...

Page 27: ...itted on the cold side Set the switch to 1 Check the settings on the control computer and adjust so there is a need of heating The blue indication is shown in the window on all four the valves on the...

Page 28: ...on ing The pump runs continuously Selector switch for heating medium pumps A and B If there is an external circulation pump the nor mal position is Auto If not set HMP A to Man Selector switch for com...

Page 29: ...crease Reduce heating knob heating curve off set can then be set 30 40 50 60 70 C FRAMLEDNINGSTEMPERATUR 40 C UTETEMPERATUR 10 0 10 20 30 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 5 5 20 30 40 20 10 0 V RME...

Page 30: ...aller 28 LEK LEK 77 87 16 19 35 4 86 71 73 72 70 76 78 5 96 96 LEK LEK 65 17 27 7 42 48 41 18 28 33 LEK Svart Vit Gr Brun R d R d Gr Gr 1 R 0 2 2 max min 38 68 2 21 30 29 34 31 69b 69a 95 97b 97a 8 13...

Page 31: ...ice connection low pressure 48 a b Expansion valve 52 Safety valve heat transfer side 63 Particle filter 65 a b Drying filter 67 Relay 68 Contactor compressor start 69 a b Contactor compressor operati...

Page 32: ...ller AJ 121 122 130 129 131 132 133 123 124 125 126 127 128 134 A Cirk pump V rmepump Varmvatten Tillsatsv rme Larm Kontrollera att vatten finns i pan nan innan 1 R 0 P B P FIGHTER 1310 HPAC AB B A VX...

Page 33: ...0 PE X29 15 X29 17 X29 21 X29 22 X29 23 5 3 1 2 4 6 6 4 2 R S C X29 3 X9 N PE X29 24 X13b 5 2 8 33a P 33b 26a 26b 37 25a 25b 40 69a 69b 39a 39b 68 68 36b 36a 69a 1 3 5 68 26a 69a Re6 X9 18 X29 10 X6 1...

Page 34: ...110 540 725 815 1145 Cirk pump V rmepump Varmvatten Tillsatsv rme Larm Kontrollera att vatten finns i pan nan innan den in kopplas 1 R 0 600 Kabelintag givare Kabelintag starkstr m matning A clear spa...

Page 35: ...Dimensions 33 For the Installer FIGHTER 1310 HPAC 600 400 200 400 100 80 80 687 927 80 514 231 67 493 121 122 123 124 125 126 127 128 134 Dimensions and setting out coordinates HPAC...

Page 36: ...ed in the FIGHTER 1310 behind the front service cover by the upper module LEK NIB E AB Ute tem per atur giva re Out doo r tem pera ture sen sor Aus sen tem pera tur f hl er Artik el 018 764 Enclosed k...

Page 37: ...35 C kW 23 3 4 9 29 3 6 2 34 0 7 5 Stated cooling output Supplied output at 12 35 C kW 30 5 3 35 6 6 41 8 2 Protection motor charact slow A 25 Connection heating medium ext mm 2 x 28 35 Collector flow...

Page 38: ...uses Cause The compressor does not start because of a too low value set on the heating curve Action Check and possibly raise the Increase reduce heat knob on the front panel or Curve slope Cause The c...

Page 39: ...use on the relay card has blown Action Replace the fuse Alarm lamp flashes and the text LPalarm is displayed Cause Bad circulation in heat transfer system due to inferior venting low pressure or ice i...

Page 40: ...ain valve 78 Draining collector side Draining the building s distribution system Shut down FIGHTER 1310 by turning the switch 8 to 0 Open the front cover Loosen the air screw with a screwdriver Hold a...

Page 41: ...pump rotor If it sits firmly it can be loosened by knocking the rear of the shaft fig B Clean inside the stator can using a cleaning agent fig C Also clean the rotor unit using the cleaning agent and...

Page 42: ...FIGHTER 1310 HPAC For the Installer 40...

Page 43: ......

Page 44: ...R NIBE AB SWEDEN Box 14 J rnv gsgatan 40 SE 285 21 MARKARYD Tel 46 0 433 73 000 Fax 46 0 433 73 190 www nibe com...

Reviews: