Control, double curves
FIGHTER 1310
For Home Owners
12
Available information and on-display settings
Brine In
Temperature of the incoming brine.
Brine Out
Temperature of the outgoing brine.
[P]
(Minimum permitted temperature for the brine
return from the heat pump).
This setting should only be changed by a special-
ist. It is used for minimum limiting with alarm, for
example as an anti-freezing function in ground-
water systems or exhaust air systems.
A suitable setting with an intermediate heat
exchanger would be 0 °C. When the lowest value
(-12) is set, minimum limiting and the alarm are
disabled.
Setting range: -12 - +10 °C.
HW stop
The current temperature at the bottom part of the
water heater’s outer shell.
[P]
(Chosen stop level for hot water production.)
Setting range: 15 - 70 °C or A.
3b
4
Room-comp **
[P]
When the room temperature deviates by 1
degree C, the WW-out set point is changed by
the value indicated.
A higher value gives a quicker reaction if the
temperature in the premises is too high or too
low. The normal value for a radiator system is 4.
Setting range: 0 - 6 °C
5*
*
Displayed only if more than one heat pump is
installed (i.e. if the chosen value for HP-no. in menu
18 is > 0).
** Only displayed if a room sensor (RG20) is connect-
ed.
Curveslope
[P]
Set heat curves.
Setting range: 1 – 15
5b
5c**
Parallel *
[P]
When the chosen HP-no. setting (menu 18)>
0, the parallel offset is set by programming in this
menu instead of setting with the knob.
Setting range: -10 – +10
WW-in
Current temperature of incoming heating water.
[P]
(Max permitted return temperature for com-
pressor operation.)
Setting range: 40 - 60 °C.
HW start
The current temperature at the bottom part of the
water heater’s outer shell.
[P]
(Chosen start level for hot water production.)
Setting range: 5 - 60 °C.
3
Curveslope 1
9
Curveslope 2
7
Parallel 1
2
Parallel 2
0
Room-comp
4 °C
WW-in
37(46) °C
HWstart
49(44) °C
WW-in
37(46) °C
HW-stop
49( A) °C
BrineIn
+3 °C
BrineO-
0(-12) °C