Control, normal
9
For Home Owners
FIGHTER 1310
Brine In
Temperature of the incoming brine.
Brine Out
Temperature of the outgoing brine.
[P]
(Minimum permitted temperature for the brine
return from the heat pump).
This setting should only be changed by a special-
ist. It is used for minimum limiting with alarm, for
example as an anti-freezing function in ground-
water systems or exhaust air systems.
A suitable setting with an intermediate heat
exchanger would be 0 °C. When the lowest value
(-12) is set, minimum limiting and the alarm are
disabled.
Setting range: -12 - +10 °C.
WW-in
Actual temperature of incoming heating water.
[P]
(Max permitted return temperature for com-
pressor operation.)
Setting range: 40 - 60 °C.
HW start
The current temperature at the bottom part of the
water heater’s outer shell.
[P]
(Chosen start level for hot water production.)
Setting range: 5 - 60 °C.
3
WW stop
Actual temperature in lower part of water heater
outer jacket.
[P]
(Chosen stop level for hot water production.)
Setting range: 15 - 70 °C or A.
3b
4
Available information and on-display settings
Curveslope
[P]
Set heating curve.
Room-comp **
[P]
When the room temperature deviates by
1 °C, the WW-out set point is changed by the
value indicated.
A higher value gives a quicker reaction if the
temperature in the premises is too high or too
low. The normal value for a radiator system is 4.
Setting range: 0 - 6 °C
5b**
5*
*
Displayed only if more than one heat pump is
installed (i.e. if the chosen value for HP-no. in
menu 18 is greater than > 0).
** Only displayed if a room sensor is connected.
Curveslope
[P]
Set heating curve.
Setting range: 1 – 15
Parallel *
[P]
When the chosen HP-no. setting (menu 18) is
>0, parallel offset is set by programming in this
menu instead of setting with the knob.
Setting range: -10 – +10
Curveslope
9
Parallel
0
Curveslope 9
Room comp
4 °C
WW-in
37(46) °C
HW start 49(44) °C
WW-in
37(46) °C
WW-stop
49(A) °C
Brine In
+3 °C
Brine 0
0(-12) °C