Technical specifications
20
14
3x400V
Output data at nominal flows
1)
23.6/6.43/3.68
17.0/4.49/3.79
kW/kW/-
15/55
Delivered / Supplied power / COP
19.6/4.22/4.63
14.1/2.96/4.77
kW/kW/-
7/35
Delivered / Supplied power / COP
17.9/5.11/3.49
13.1/3.58/3.65
kW/kW/-
2/45
Delivered / Supplied power / COP
14.6/4.92/2.96
10.7/3.50/3.06
kW/kW/-
-7/45
Delivered / Supplied power / COP
15.2/5.95/2.55
11.0/4.24/2.59
kW/kW/-
-7/55
Delivered / Supplied power / COP
12.7/5.69/2.23
9.16/4.11/2.23
kW/kW/-
-15/55
Delivered / Supplied power / COP
Output data according to EN 14511
2)
20.85/4.47/4.66
15.49/3.20/4.84
kW/kW/-
10/35
Delivered / Supplied power / COP
EN14511
17.7/4.37/4.04
13.8/3.14/4.39
kW/kW/-
7/35
Delivered / Supplied power / COP
EN14511
18.3/5.38/3.41
14.1/3.83/3.69
kW/kW/-
7/45
Delivered / Supplied power / COP
EN14511
19.04/6.55/2.91
15.22/4.78/3.18
kW/kW/-
7/55
Delivered / Supplied power / COP
EN14511
15.46/4.38/3.53
11.84/3.08/3.84
kW/kW/-
2/35
Delivered / Supplied power / COP
EN14511
15.95/5.28/3.02
12.27/3.74/3.28
kW/kW/-
2/45
Delivered / Supplied power / COP
EN14511
12.83/4.32/2.97
9.41/3.03/3.10
kW/kW/-
-7/35
Delivered / Supplied power / COP
EN14511
13.28/5.15/2.58
9.72/3.66/2.65
kW/kW/-
-7/45
Delivered / Supplied power / COP
EN14511
10.37/4.2/2.47
7.49/2.96/2.53
kW/kW/-
-15/35
Delivered / Supplied power / COP
EN14511
10.73/4.97/2.16
7.74/3.52/2.20
kW/kW/-
-15/45
Delivered / Supplied power / COP
EN14511
Electrical data
400V 3NAC 50 Hz
Rated voltage
16
12
A
rms
Max operating current, heat pump
12.8
8.2
A
rms
Max operating current, compressor
39.6
30
A
rms
Starting current
-
-
Ohm
Max permitted impedance at connection point
3)
100/224
100/224
W
Nominal output fan (low/high)
16
16
A
rms
Fuse
Refrigerant circuit
R407C
Type of refrigerant
Scroll
Type of compressor
2.8
2.2
kg
Volume
3.2 (32 bar)
MPa
Cut-out value pressostat HP
-0.7 (-7 bar)
MPa
Difference pressostat HP
0.02 (0.2 bar)
MPa
Cut-out value pressostat LP
0.05 (0.5 bar)
MPa
Difference pressostat LP
Brine
3700/6000
3700/6000
m
3
/h
Air flow (low/high)
-25/40
°C
Min/Max air temp
hot gas defrosting
Defrosting system
Heating medium
0.05/0.3 (0.5/3 bar)
MPa
Min/Max system pressure heating medium
0.47/0.94
0.33/0.67
l/s
Nominal flow
4)
(Min flow during defrosting.)
0.47
0.33
l/s
Min/Max flow
4.5
4.5
kPa
Internal pressure drop at nominal flow
NIBE™ F2300
Chapter 8 |
Technical data
36
Summary of Contents for F2300
Page 1: ...Service manual LEK NIBE F2300 Air water heat pump SEM GB 1335 1 M11450 ...
Page 2: ......
Page 33: ...Electrical circuit diagram 31 Chapter 8 Technical data NIBE F2300 8 Technical data ...
Page 34: ...NIBE F2300 Chapter 8 Technical data 32 ...
Page 35: ...33 Chapter 8 Technical data NIBE F2300 ...
Page 36: ...NIBE F2300 Chapter 8 Technical data 34 ...
Page 42: ......
Page 43: ...NIBE AB Sweden Hannabadsvägen 5 Box 14 SE 285 21 Markaryd info nibe se www nibe eu ...