ADVANCED
advanced 4.9
op. prioritisation
auto mode setting
degree minute setting
factory setting user
schedule blocking
off
Menu
advanced
has orange text and is
intended for the advanced user. This menu
has several sub-menus.
Menu
4.9
OP. PRIORITISATION
op. prioritisation4.9.1
min
min
min
hot water
heating
pool
30
30
30
op. prioritisation
Setting range: 0 to 180 min
Default value: 30 min
Choose here how long the heat pump should work with each requirement if
there are two or more requirements at the same time. If there is only one require-
ment the heat pump only works with that requirement.
The indicator marks where in the cycle the heat pump is.
If 0 minutes is selected it means that requirement is not prioritised, but will only
be activated when there is no other requirement.
Menu
4.9.1
NIBE F1255PC
BE
Chapter 3 | F1255PC BE – at your service
70