32
General
This manual contains instructions about how the
Contura 580W must be constructed and installed.
To ensure the function and safety of the stove, we
recommend that the installation is carried out by an
authorised technician. Instructions for lighting and
use are also supplied with the stove. Read them
carefully and keep them safe for future use.
The stove is type approved and must be connected
to a chimney dimensioned for at least 350°C, the
external connection diameter is Ø150 mm.
Supply air from the open air should be used as com-
bustion air.
Technical specifications
Output
3 – 7 kW
Nominal output
5 kW
(approx. 1.5 kg wood/hour)
Efficiency, up to
80%
Connector ext.
Ø150 mm
Weight
.......................
100 kg
Width
..........................
500 mm
Depth
..........................
440 mm
Height
........................
740 mm
Type approved in accordance with:
European standard EN-13240 class 1
Swedish environmental and quality marking, P-marking cert. no.
22 03 09
Swedish type approved, cert.no. 0222/03
Norwegian standard NS 3059, Cert. No. 043-140
German standard DIN 18.891, RO-91 03 529
Danish standard DS/EN 13240 plus, id no. 598
Building application
Before installing a stove or erecting a chimney it is
necessary for you to make a building application
permission to your local authority. Ask your local
authority for advice regarding building regulations
and the application.
Eldstadsbeklädnad
Rostertallrik
Asklåda
Rökhylla
Structural design
The instructions indicate how Nibe recommends the
stove is installed. Always check with an authorised
chimney sweep that the installation method is an
approved method and that the chimney/walls have
sufficient support before starting installation.
Hearth plate
To protect the floor from any embers the
stove must be supplied with a hearth plate. If
the floor under the stove is flammable, it must be
protected by a non-flammable material. The hearth
plate can consist of natural stone, concrete or 0.7
mm metal.
As the requirements for the size of the hearth plate
can vary at different installation heights, you should
check what is applicable with your chimney sweep.
In general the hearth plate must protrude at least
300 mm in front of the stove and at least 100 mm
to the side.
If the bottom of the stove is 400 mm above the floor,
the distance must be increased by half the protrud-
ing height. This should be checked with your chim-
ney sweep.
Chimney
The stove requires negative pressure in the chimney
of at least 12 Pa. The negative pressure is affected
both by the length and area of the chimney, and by
how well sealed it is. Minimum recommended chim-
ney length is 3.5 m and a suitable cross section area
is 150-200 cm² (140-160 mm in diameter).
Carefully check that the chimney is sealed and that
there is no leakage around soot hatches and flue
connections.
Note that a flue with sharp bends and horizon-
tal routing reduces the draught in the chimney.
Maximum horizontal flue is 1 m, on the condition
that the vertical flue length is at least 5 m.
It must be possible to sweep the full length of the flue
and the soot hatches must be easily accessible.
GB
Grate disc
Ash-pan
Fire-box surround
Smoke baffle