Hot Water Storage Tank with Two Coils

BA-ST 9022/9100 - 2FE

DHW

supply from the upper coil

hot water circulati on
return from the upper coil

supply of the lower coil

return from the lower coil

to sewerage

water supply system

1.  BA-ST storage tank

2.  Cut-off  valve

3.  Safety valve

4.  Drain valve

5.  Pressure reducer (opti on, if the pressure in the 

system exceeds the allowable value)

6.  Strainer

7.  Hot water circulati ng pump

8.  C/H circulati ng pump

9.  Hot water expansion vessel

Fig. 9 

Installati on diagram of the BA-ST storage tank with two coils.

4. CONNECTION AND START-UP

4.1 Connecti on

1.  Remove protecti ng plugs from the connector pipes

2.  Connect the hot water intake line (12).

3.  Connect  the  cold  water  supply  line  together  with  the 

required safety valves (19).

4.  If the system has the hot water circulati on system, con-

nect it to the connector pipe (14). Otherwise, plug the 

pipe.

5.  Connect the supply (13) and return (16) of the heati ng 

medium to the upper coil.

6.  Connect the supply (17) and return (18) of the heati ng 

medium to the lower coil.

1

2

2

2
2

2

2

2

2

2

2

6

6

6

8

7

8

3

9

4

5

4.2 Start-Up

Fill the storage tank with water and vent it aft er making cor-

rect connecti ons.

If there is an electric heati ng module installed in the 

storage tank, fi ll the tank with water before connecti ng 

it to the electrical installati on.

CAUTION

1.  Open the cold water cut-off  valve at the inlet and the hot 

water intake point

2.  Fill  the storage tank unti l obtaining uniform water out-

fl ow at the hot water intake point. Close the intake points

3.  Fill the upper and lower coils with the heati ng medium, 

and vent them

4.  Check ti ghtness of the enti re system

When properly fi lled and vented, the storage tank is ready to 

use.

Aft er the installati on and levelling the tank, follow the proce-

dure below (for the connector pipe numbers, refer to Fig. 3 

and Fig. 5):

Filling and venti ng the hot water storage tank:

Open the hot water intake valves before heati ng the 

system up for the fi rst ti me or aft er a longer break in its 

operati on in order to check whether the storage tank is 

fi lled with water and the cut-off  valve at the cold water 

inlet is not closed.

CAUTION

4.4 Warnings and Practi cal Recommendati ons

•  Check the operati on of the safety valve as described by 

the manufacturer of the valve in order to check whether 

it is not clogged.

•  Clean the inside of the storage tank periodically. Cleaning 

intervals depends on the hardness of the water present 

in a given area.

•  To ensure opti mum protecti on of the storage tank against 

corrosion, we recommended checking the level of wear 

of the isolated magnesium anode once a year.

We recommend the following:

4.3 Thermal Insulati on of the System

In order to minimize thermal energy losses, insulate all con-

nector pipes, pipelines and temperature sensor covers tho-

roughly aft er the installati on of the unit and performance of 

the leak proof test. For this purpose, use thermal insulati on 

of correctly selected thickness and thermal insulati on para-

meters.

Lack of thermal insulati on, its incorrect thickness or in-

sulati on made of inadequate materials will cause decre-

ase of thermal insulati on properti es of the unit and the 

system.

Informati on

We  recommend  connecti ng  the  tank  connector  pipes 

with the system lines by means of unions to allow discon-

necti on of the tank, if required.

Informati on

To  prevent  bacterial  growth  we  recommend  to  make 

sure a periodically increase of hot water temperature for 

a shorter ti me at regular intervals e.g. every 14

th

 day.

CAUTION

INSTALLATION AND OPERATING MANUAL

Summary of Contents for BA-ST 9022 - 2FE

Page 1: ...Installation and Operating Manual Hot Water Storage Tank with Two Coils BA ST 9022 2FE BA ST 9030 2FE BA ST 9040 2FE BA ST 9050 2FE BA ST 9075 2FE BA ST 9100 2FE 22 02 2016 25621...

Page 2: ...product design changes and changes in the manual NIBE 2016 CONTENT 1 GENERAL 3 1 1 Introduction 3 1 2 Intended Use 3 2 DESIGN 4 3 INSTALLATION 6 3 1 Location of the Storage Tank 6 3 2 Housing Disassem...

Page 3: ...ge tank enables trouble free operation with al most any central heating system with forced circulation They are easy to install safe and comfortable to use if installed and operated in accordance with...

Page 4: ...xcellent thermal insulation properties of all devices Storage tanks have aesthetic plastic housing a temperature indicator inspection opening and connectors for mounting electric heating unit and conn...

Page 5: ...r 10 Connector pipe for mounting electric heating unit 11 Inspection opening 12 Hot water intake connector pipe 13 Upper coil supply connector pipe 14 Hot water circulation connector pipe 15 Temperatu...

Page 6: ...ions or the appropriate magnesium chain anode For the speci cation of the protective anodes available at NIBE see Section 6 Accessories and Spare Parts Amin Fig 6 Min clearance for the replacement of...

Page 7: ...e to the sewerage or drain grate Safety valve drain line should be installed with a decline in an environment free of freezing and remain open to the atmosphere The manufacturer is not responsible for...

Page 8: ...vented the storage tank is ready to use After the installation and levelling the tank follow the proce dure below for the connector pipe numbers refer to Fig 3 and Fig 5 Filling and venting the hot wa...

Page 9: ...aning of the storage tank 5 1 Inspection of the Protective Magnesium Anode Storage tanks with two coils of BA ST Series are in order to protect them against corrosion coated inside with ceramic enamel...

Page 10: ...ntervals Storage tank cleaning procedure During mechanical cleaning be careful to not damage the enamel In the case of chemical cleaning pay special attention to neutralize the chemicals used for clea...

Page 11: ...BA ST 9022 2FE ME 1500 1 5 kW 1 ME 2000 2 0 kW 1 WP 6 81 4 0 kW 1 BA ST 9030 2FE BA ST 9040 2FE BA ST 9050 2FE WP 6 8 4 5 kW 1 MEL 1030 3 0 kW 1 MEL 1060 6 0 kW 1 BA ST 9075 2FE WP 12 12 0 kW 2 MEL 2...

Page 12: ...4 9 38 8 5 8 5 Lower coil area m2 1 4 1 6 2 13 2 74 2 74 Lower coil volume l 4 2 9 38 13 16 16 Max tank operating temp C 85 Max allowable instantaneo us temp in the tank C 98 Max coil operating temp...

Page 13: ...sions F F E E D D P O N M L K J I H G D D E E F F G G H H I I J J K K L N M L N M O O P P R R W W Fig 15 Dimensions of the BA ST 9022 9050 2FE storage tanks Fig 16 Dimensions of the BA ST 9075 9100 2F...

Page 14: ...male H Return from lower coil inch Male 1 Male G Cold water input inch Male 1 Male 1 Male Dimensions BA ST 9022 2FE BA ST 9030 2FE BA ST 9040 2FE BA ST 9050 2FE BA ST 9075 2FE BA ST 9100 2FE B mm 665...

Page 15: ......

Page 16: ...ielle RD 28 Rue du Pou du Ciel 01600 Reyrieux Tel 04 74 00 92 92 Fax 04 74 00 42 00 E mail info nibe fr www nibe fr FR NIBE Energy Systems Ltd 3C Broom Business Park BridgeWay Chesterfield S41 9QG Tel...

Reviews: