Pump adjustment, manual operation
Brine side
GreenMaster-HP has brine pumps that are automatically
controlled. For manual operation: deactivate “auto” in
menu 5.1.9 and then set the speed according to the
diagrams below.
Caution
When an accessory for passive cooling is used,
the brine pump speed must be set in menu
5.1.9.
Heating medium side
To set the correct flow in the climate system, the correct
speed must be set for the heating medium pump in the
different operating conditions. GreenMaster-HP has a
heating medium pump that can be automatically con-
trolled, but if manual speed is desired, it is set according
to the following information. For manual operation,
"auto" must be deactivated in menu 5.1.11.
Set the speed of the heating medium pump in the menu
5.1.11, see the Operating Manual.
GreenMaster-HP 6 kW
Available pressure, kPa
Flow l/s
Electrical input, W
Pumpkapacitet, värmebärarsida för F1155-1255 -6 kW, manuell drift.
Tillgängligt tryck
kPa
Eleffekt
W
0
0,00 0,05 0,10 0,15 0,20 0,25 0,30
0,45
0,40
0,35
0,50
30
10
20
40
50
60
70
80
90
0
70
60
50
40
30
20
10
Flöde l/s
P100%
P80%
100%
80%
60%
40%
P40%
P60%
GreenMaster-HP 16 kW
Available pressure, kPa
Flow l/s
Electrical input, W
Pumpkapacitet, värmebärarsida för F1155-1255 -16 kW, manuell drift.
Tillgängligt tryck
kPa
Eleffekt
W
0
0,00
0,10
0,05
0,15
0,25
0,20
0,35
0,30
0,45
0,40
0,50
30
10
20
40
50
60
70
80
90
0
100
90
80
60
70
40
50
30
10
Flöde l/s
20
P100%
P80%
100%
80%
60%
40%
P40%
P60%
Readjusting, venting, heat medium side
Initially, air is released from the hot water and venting
may be necessary. If gurgling sounds can be heard from
GreenMaster-HP or the climate system, the entire system
requires additional venting.
Readjusting, venting, collector side
Expansion vessel
LEK
Check the pressure level in the pressure ex-
pansion vessel (CM3) in GreenMaster-HP. If
the pressure drops, the system should be
replenished.
Post adjusting the room
temperature
If the required room temperature is not obtained, read-
justment may be necessary.
Cold weather conditions
■
When the room temperature is too low, increase
"heating curve" in menu 1.9.1.1 by one increment.
■
When the room temperature is too high, reduce
"heating curve" in menu 1.9.1.1 by one increment.
Warm weather conditions
■
When the room temperature is too low, increase
"temperature" (offset heating curve) in menu 1.1.1 by
one increment.
■
When the room temperature is too high, reduce
"temperature" (offset heating curve) in menu 1.1.1 by
one increment.
GreenMaster-HP
Chapter 6 |
Commissioning and adjusting
36