If rotation in both directions is required (e.g. at ±10V or ±10mA, stopping in the middle), set 

Min Ain Spd

 to negative 

(–) 

Max Ain Spd

5.11  Process regulation, PI regulator 

The inverter is equipped with a PI regulator used for process regulation with an external actual value (sensor 
signal) according to a selected setpoint value. The regulator can be used in both control mode 

Frequency

 and 

Speed

. The regulator is enabled by either setting the 

Op Mode (Setp Source)

 parameter to 

PI-Reg

 in the control 

mode used, or setting the correct digital input combination at the terminal if 

Terminal

 is the selected

 

source. For 

backward compatibility with older NFO Sinus inverters, the process regulator can also be activated by setting 
parameter 

Control Mode = PI-Reg

 

 

Fig. 13. Process regulator overview 

The process regulator unit (default kPa) is selected using the parameter 

Unit 

(both setpoint and actual value), see 

Table 14. Whatever setpoint source is used, the regulator's actual value is by default taken from the analog input 
AIN2 at terminal 22. The scaling of the actual value is controlled by parameters 

Actual Min 

och

 Actual Max

 which 

translates the minimum and maximum signal level from the actual value input corresponding to the selected unit.  

The regulator generates an output signal in the form of a setpoint (frequency or speed) in the range limited by 
parameters 

Min Frq

 and 

Max Frq, or Min Spd

 and 

Max Spd, 

depending on the control mode chosen. When using 

Control Mode = PI-Reg

 the parameters used for scaling min and max frequency are 

Min Freq

 and 

Max Freq

If a potentiometer or a sensor is used for the setpoint, their output signal is scaled to the chosen regulator unit by 
parameters 

Setpoint Min

 and 

Setpoint Max

. With parameters 

Setpoint Min Limit

 and 

Setpoint Max Limit

, it is 

possible to limit the range of the setpoint value. 

Both AIN1 and AIN2 can be configured for voltage or current input individually, see 4.1.3, Table 8 and Table 15. 

If desired, the parameters 

Reg Off Limit

 and 

Reg On Limit

 can be used to turn off motor when a certain actual value 

has been reached, and then again turn on motor when actual value has dropped below the turn on limit. When any 
of the parameters

 Reg Off Limit

 or 

Reg On Limit

 are zero, this functionality is disabled. The turn off function uses 

the sleep frequency, therefore the sleep functionality cannot be used concurrently for some other purpose. 

The regulator's sampling rate is 10 samples per second. 

 

3006469-2022-04

Summary of Contents for NFO 3A4D3490D

Page 1: ...www nfodrives se info nfodrives se 46 454 370 29 Tubba Torg 5 SE 374 32 Karlshamn Sweden Operating and Installation Manual NFO Sinus Optimal 3006469 2022 04...

Page 2: ...l notes 15 5 2 Keyboard and display 15 5 3 Indicators and Motor status 17 5 4 Operating modes 17 5 4 1 Manual Mode 18 5 4 2 Auto Mode 18 5 4 3 Bus Mode Serial channel Field bus 19 5 5 Parameter specif...

Page 3: ...elay 2 Run indication 36 5 13 3 Analog outputs 36 5 14 Communication interfaces 36 5 15 Display setup 37 5 16 Status Temperature Counters and Version 37 5 17 Reset to factory settings 37 5 18 Alarm an...

Page 4: ...l section are connected to the mains supply when the inverter is powered WARNING Touching any components with the mains supply connected can be fatal Always disconnect the mains supply before opening...

Page 5: ...requency and 100 of rated output current 5 CDM Complete Drive Module efficiency class according to Commission Regulation EU 2019 1781 and IEC 61800 9 2 2017 6 Due to sinusoidal voltage output from the...

Page 6: ...input PTC or Klixon Electronic motor overload protection Switch off if motor load is over rated power for a long time Ambient conditions Ambient operating temp 10 45 C Storage temp 20 60 C Humidity 0...

Page 7: ...or cover is not allowed After installation make sure all grommets at the cable entries are mounted and the cover is closed and secured with its screws to avoid contact with dangerous voltages 3 1 Moun...

Page 8: ...nted between the inverter terminals U V and W and the motor but it must only be operated when the motor is not running First time powered up the installer must select application enter motor name plat...

Page 9: ...3 2 5 mm AWG 26 AWG 14 To connect the cable carefully push the actuator downward If a tool is used make sure it does not damage any components on the circuit board The signal cables should be fixed to...

Page 10: ...N Analogue input 2 neg Process regulator actual value input negative 0V I O Ground 24 AOUT1 I Analogue output 1 I Current output 1 25 AOUT1 U Analogue output 1 U Voltage output 1 impedance 50 26 AOUT...

Page 11: ...ollowing sections Fig 2 Jumper placement and default settings 4 1 3 Analogue current input To use analogue current input 1 move J701 to I position If more than one unit is controlled by a single curre...

Page 12: ...olled via an RS485 type serial channel Connection is made through terminals 32 RS485 A and 34 RS485 B If the signals are to be bridged to further units terminals 33 and 35 can be used as in Fig 5 Term...

Page 13: ...r B Brake resistor Connection for external brake resistor between B and Internal DC link voltage negative and positive terminals Positive terminal also used for external brake resistor option PE Prote...

Page 14: ...A motor with a nominal voltage of 400V Y 230V D must be configured for Y connection and a motor with nominal voltage of 690V Y 400V D must be configured for D connection Setup of motor parameters and...

Page 15: ...r into parameter or parameter group Save parameter Enter toggle between normal screen and setup menu tree Leave parameter parameter group or leave parameter unsaved Toggle Operating mode between Manua...

Page 16: ...rating and Installation Manual 16 The following flowchart Fig 9 shows how different screens are reached examples of appearance and explanation of text Fig 9 Programming flowchart and screen examples w...

Page 17: ...he inverter with an external start signal from terminal 1 DIN1 The Manual mode is normally used for test and programming as well as running the inverter with the use of the keyboard The inverter will...

Page 18: ...e and run signal terminal 1 DIN1 is not active the Motor status shows Standby The source for the setpoint is selected by the parameter Op Mode Setp Source for the control mode concerned see 5 9 1 5 10...

Page 19: ...ue Input terminal 0 20 mA Current 0 20mA 20 and 21 J701 at I position 4 20 mA Current 4 20mA 20 and 21 J701 at I position 20 mA Current 20mA 20 and 21 J701 at I position 0 10 V Voltage 0 10V 20 J701 a...

Page 20: ...lay FixFrq5 FixSpd5 FixReg5 Aout 1 Max RS485 autostop Brake chop Heat sink 3 Menu readonly Start count PTC Temp Tuning DC brake FixFrq6 FixSpd6 FixReg6 Aout 2 Mode RS485 failsafe Stator freq Heat sink...

Page 21: ...elay from motor has stopped until new Run signal is accepted 0 0 s 0 0 10 0 s Stby Run DC Brake Time in seconds for motor DC braking before start 0 s 0 10 s Stby Run Kp speed Amplifier component speed...

Page 22: ...0 0 Stby Run Reg On Limit Turn on motor when actual value above on limit 0 0 2000 0 2000 0 Stby Run Output Relay 1 Mode Disable Function disabled Running Motor running Run Fwd Motor running forward Ru...

Page 23: ...l input current mA Read Keyboard Bitmask input of keyboard Read Terminals Bitmask input of terminals DIN1 8 Read Temperature Motor temp Estimated motor temperature in percent of max Read Power module...

Page 24: ...ers the installer will be prompted to select application type for the inverter The purpose of selecting application is to preset acceleration and deceleration ramps to a value suitable for the applica...

Page 25: ...lowable limit for the inverter If the auto tuning process results in an error the cause of error must be identified and corrected before the motor can be started Faults may be due to Motor not connect...

Page 26: ...has a nominal frequency of 50Hz and is to accelerate from 0 to 80 Hz in 2 sec and brake from 80 to 5 Hz in 9 sec tAccel 50 2 80 1 25 s tDecel 50 9 75 6 00 s The inverter cannot accelerate faster than...

Page 27: ...the time from when inverter is powered until it accepts a start command PowerOn Delay can be useful to handle short time power failures interrupts and restarting when operating with large inertial to...

Page 28: ...d motor model Estimated speed ac tual value Integrator c omponent Fig 11 Speed regulator If you have any doubts or problems please contact NFO Drives AB 5 8 8 Frequency sleep setting This function is...

Page 29: ...max current limit Use the parameters Boost time to set the time after start in seconds and Boost Level 0 100 of exceeding current capacity to set the increased current limit during boost time period...

Page 30: ...7 Analog 1 F Analogue input 1 clockwise Analog 1 R Analogue input 1 counter clockwise Analog 2 F Analogue input 2 clockwise Analog 2 R Analogue input 2 counter clockwise Fix 1 F Frequency from paramet...

Page 31: ...rom parameter Fix Spd 4 clockwise Fix 5 F Speed from parameter Fix Spd 5 clockwise Fix 6 F Speed from parameter Fix Spd 6 clockwise Fix 7 F Speed from parameter Fix Spd 7 clockwise Fix 1 R Speed from...

Page 32: ...al Min och Actual Max which translates the minimum and maximum signal level from the actual value input corresponding to the selected unit The regulator generates an output signal in the form of a set...

Page 33: ...1 clockwise Analog 1 R Analogue input 1 counter clockwise Analog 2 F Analogue input 2 clockwise Analog 2 R Analogue input 2 counter clockwise Fix 1 F Setpoint from parameter Fix Reg 1 clockwise Fix 2...

Page 34: ...an be set to 1 a positive or increasing value of the output signal if the regulator setpoint is greater than the current actual value or 1 a negative or decreasing value of the output signal if the re...

Page 35: ...load The final value of 100 0 corresponds to nominal load and the electronic motor overload protection trips when this value is passed The ambient motor temperature is set with parameter Amb Temp in t...

Page 36: ...U and terminal 27 AOUT2 U and current output at terminal 24 AOUT1 I and terminal 26 AOUT2 I respectively Both are related to any of the 0V terminals To scale the output use parameter Aout 1 2 Max cur...

Page 37: ...e selectable actual values are shown lower left middle and right position By default the actual values of IRMS PRMS and PF power factor are shown respectively Users may change these values by altering...

Page 38: ...g Some faults have to persist for a given time Delay before they generate a fault Motor Fault e g AC fail ErrCnt 2 RstDly RstDly RstDly RstDly T rT ime T rT ime RstDly isreset Fig 14 Typical fault sit...

Page 39: ...setpoint or Ain Type not set correctly DC Low Trip Fail Fail 2 DC link voltage too low or supply is disconnected Power supply voltage too low Check inverter mains connection DC High Fail Fail 2 DC li...

Page 40: ...00h to parameter SMODE Modbus register 0298h NFO Classic E00AD 6 Communication using Modbus Modbus RTU or Modbus ASCII can be used for communication with the inverter Available communication ports are...

Page 41: ...tick per every 36 s Read only Running Time 40 02ACh 02ADh UINT32 h 102 one tick per every 36 s Read only Serial Control Parameters MODE 34 0294h UINT16 1 Manual 2 Auto 3 Bus SMODE Command 35 0298h UIN...

Page 42: ...nt too low 43 Calibr Done Calibrate procedure finished 12 Cur High Output current too high 44 BasicTun Ok Basic tuning finished 13 Run Fail Locked rotor unable to control motor 45 Full Tun Ok Full tun...

Page 43: ...re ack 15 Stopping Inverter is decelerating towards a stop An example of communication could be that bus master sets the Bus control command bit and then waits for inverter to respond with Control fro...

Page 44: ...rter to respond with Enabled Now the bus master may start the motor using the Switch on command bit and inverter will respond with bit Operating When master clears the Switch on bit inverter will dece...

Page 45: ...t direction Press MAN AUTO to go to Manual mode Set the frequency desired in display window Use and to change setpoint Positive frequency setpoint means clockwise rotation negative means counter clock...

Page 46: ...PI reg Set actual value sensor measures at 10V 300 kPa using parameter Actual Max in parameter group PI reg Set the regulator amplification using parameter Reg Kp in parameter group PI reg Set regula...

Page 47: ...0 AIN1 P positive and terminal 21 AIN1 N negative that gives the desired night time low frequency setting Connect a time relay or other contact between DIN4 PI reg and a 24V source When DIN4 terminal...

Page 48: ...NFO Drives AB 2021 201013 2 Operating and Installation Manual 48 3006469 2022 04...

Reviews: