Parameter
Unit
and
Sense Unit
settings
Parameter
Ain
Type
settings
Analogue value
Input (terminal) and jumper
setting
Pa, kPa, bar, rpm,
0-10V
Voltage 0-10V
22 (J703 at “U” position)
m
3
/s, l/s, m
3
/h, l/h,
2-10V
Voltage 2-10V
22 (J703 at “U” position)
ppm, %, V, Hz,
+/-10V
V/- 10V
22 (J703 at “U” position)
Nm, m, W, A,
0-20mA
Current 0-20mA
22 and 23 (J703 at “I” position)
Ω
, H, s, rad/s
4-20mA
Current 4-20mA
22 and 23 (J703 at “I” position)
°
C, h, Wh, - (no unit)
+/-20mA
C/-20mA
22 and 23 (J703 at “I” position)
Table 14 Process regulator units
Table 15 Actual value input setting options
5.11.1 Setpoint source for PI-reg mode
The regulator setpoint source is controlled by the parameter
Op Mode (Setp Source)
Op Mode
PI regulator setpoint source
Terminal
Any of the alternatives below, selected from terminal as in Table 17.
Analog 1 F
Analogue input 1, clockwise.
Analog 1 R Analogue input 1, counter-clockwise.
Analog 2 F
Analogue input 2, clockwise.
Analog 2 R Analogue input 2, counter-clockwise.
Fix-1 F
Setpoint from parameter Fix Reg 1, clockwise.
Fix-2 F
Setpoint from parameter Fix Reg 2, clockwise.
Fix-3 F
Setpoint from parameter Fix Reg 3, clockwise.
Fix-4 F
Setpoint from parameter Fix Reg 4, clockwise.
Fix-5 F
Setpoint from parameter Fix Reg 5, clockwise.
Fix-6 F
Setpoint from parameter Fix Reg 6, clockwise.
Fix-7 F
Setpoint from parameter Fix Reg 7, clockwise.
Fix-1 R
Setpoint from parameter Fix Reg 1, counter-clockwise.
Fix-2 R
Setpoint from parameter Fix Reg 2, counter-clockwise.
Fix-3 R
Setpoint from parameter Fix Reg 3, counter-clockwise.
Fix-4 R
Setpoint from parameter Fix Reg 4, counter-clockwise.
Fix-5 R
Setpoint from parameter Fix Reg 5, counter-clockwise.
Fix-6 R
Setpoint from parameter Fix Reg 6, counter-clockwise.
Fix-7 R
Setpoint from parameter Fix Reg 7, counter-clockwise.
Table 16. PI Reg setpoint source parameter settings
If analogue input 1 (AIN1) is selected, it is configured as shown in Table 8.
3006469-2022-04