user may adjust an output current threshold and a timer used for detecting the PC OFF status. In order to restart the PC the DCW20 toggles the output OFF and 

then ON again. User must enable in the PC BIOS the automatic start in case of supply ON. 

 Power ON screen: 

This screen is shown at power ON.  

It shows the device name, serial number and firmware version. 

 

 Status: 

This is the default view where the user can find the most relevant information about 

the device status. The system always falls back to this view after 60s of inactivity (no 

key pressed). 

 Settings: 

All the device settings are configurable from this menu.  

Use the UP/DOWN KEY to navigate through the parameters. 

Press the OK KEY to enter/exit the editing mode. 

In editing mode use the UP/DOWN KEY to change the highlighted value. 

 Info: 

Device information such as firmware version, serial number and device name is 

visible from this menu. 

 Logs: 

All the alarms and event are logged in a circular buffer and visible from this screen. 

Use the UP/DOWN KEY to navigate through the logs. 

 Wizard: 

The wizard helps the user to configure the system through a series of screens. 

 

LOGS 

 

1.

 

Time

: time at which the log occurred. 

2.

 

Date

: date at which the log occurred. 

3.

 

Name

: unique log name 

4.

 

Primary value

: optional. 

5.

 

Secondary value

: optional. 

 

Every event is logged in the device FLASH memory. From the log menu the user can view their history. Use the UP/DOWN KEYS to navigate between logs, 2 logs are visible 

simultaneously on the LCD. Logs are of 3 different kinds: 

info

alarms

 and 

events

. All 

info

 and 

alarms

 have an associated Modbus field with the current status (0 if inactive 

or 1 if active). For 

info

 and 

alarms

 a log is generated at each status transaction. In case of active alarm the front LED and the buzzer turn ON. 

 

Alarms

 

Type 

LCD name 

Description 

Battery disconnected 

Bat. discon. 

Active when no battery is detected by DCW20. 

Battery Ri too high 

Bat Ri too high 

Active when measured battery internal resistance exceed the alarm threshold 

Battery under temperature 

Bat under temp.  Active when the battery measured temperature (using the optional external sensor) is under the threshold 

specified in “

Battery min. temperature

” field. If active the battery charged is disabled. 

Battery over temperature 

Bat over temp. 

Active when the battery measured temperature (using the optional external sensor) exceed the threshold 

specified in “

Battery max. temperature

” field. If active the battery charged is disabled. 

Battery lifetime elapsed 

Bat lifetime 

Active when the actual calculated battery lifetime exceeds the threshold specified in “

Battery lifetime

” field. 

Battery charge failure 

Bat charge fail 

Active when DCW20 could not charge the battery correctly. When active, the battery charger is disabled. 

Disconnect the battery to reset the alarm. 

Battery SoC < 25% 

Bat SoC 25% 

Active when the battery State of Charge is under 25% of the nominal full charge capacity. 

Battery over discharge current 

Bat over dis. I 

Active when the measured battery discharge current reaches the threshold specified in “

Battery max. discharge 

current” 

field. 

Battery low 

Bat low 

Active when the measured battery voltage is under the threshold specified in “

Battery low voltage

” field. 

Battery deep discharged 

Bat deep disch. 

Active when the battery measured voltage is under the threshold specified in “Battery deep discharge voltage” 

field. 

Backup 

Backup 

Active when the system is in backup. 

Input under voltage 

In under volt. 

Active when the measured input voltage is under 90% of the “

Nominal output voltage

” field. 

Input over voltage 

In over volt. 

Active when the measured input voltage exceeds 120% of the “

Nominal output voltage

” field. 

Output under voltage 

Out under volt. 

Active when the measured output voltage is under 90% of the “

Nominal output voltage

” field. 

Output over voltage 

Out over volt. 

Active when the measured output voltage exceeds 120% of the “

Nominal output voltage

” field. 

Output overload 

Out overload 

Active when the measured output current reaches the threshold specified in “

Max. output current

” field. 

Input over current 

In over cur. 

Active when the measured input current reaches the threshold specified in “

Max. input current

” field. 

Auxiliary output overload 

Aux overload 

 Active when an excessive load is detected on the auxiliary output. 

External temperature sensor error  Ext. T error 

Active when the external temperature sensor is not connected while it’s use is mandatory like in NiMh battery 

charging. 

Backup time left < 25% 

Bkp left 25% 

Active when the system is in backup and the maximal backup time is less than the “

Max. backup time

” filed. 

Warning over temperature 

Warn. over T 

Active when the internal temperature is high. If the temperature increases more the device may switch OFF. 

Error over temperature 

Error over T 

Active when the internal temperature is too high. To prevent damage the device switches OFF. 

Summary of Contents for DCW20

Page 1: ...de mort Le boîtier peut produire des brûlures le laisser refroidir avant de toucher l appareil Ne faire pas pénétrer des liquides ou des corps étrangers dans l appareil Pour éviter des étincelles ne pas connecter ou déconnecter l équipement jusqu à ce que la tension d entrée a été supprimée et avant qu il n ait eut lieu la décharge des condensateurs internes minimum 1 minute INTENDED USE USO PREVI...

Page 2: ...lso possible through RS485 connection 6 Inhibit input A voltage between 5VDC and 30VDC applied to this input activates the inhibit function 7 Auxiliary output supply Maximum 5A supply from the battery unregulated 8 Input connection 2 poles are provided for input connection This must be connected to a power supply rated 12 48VDC 9 Output connection 2 poles are provided for output connection It must...

Page 3: ...h user settable limits When used as a DC DC converter the input supply must be connected to the battery connector as shown on to the side Additional Functions Battery health monitor Internal resistance measurement The resistance is periodically measured The internal resistance is a good indicator of the battery health status a sudden increase of the internal resistance indicates a potential proble...

Page 4: ...e optional external sensor exceed the threshold specified in Battery max temperature field If active the battery charged is disabled Battery lifetime elapsed Bat lifetime Active when the actual calculated battery lifetime exceeds the threshold specified in Battery lifetime field Battery charge failure Bat charge fail Active when DCW20 could not charge the battery correctly When active the battery ...

Page 5: ...harge 5 User Mounting Dismounting Instructions For DIN rail mounting according to IEC 60715 TH35 7 5 15 Mounting as shown in figure with input terminals on lower side with suitable cooling and maintaining a proper distance between adjacent devices as specified in the User manual Mounting 1 Tilt the unit slightly backwards 2 Fit the unit over the top edge of the rail 3 Slide it downward until it hi...

Page 6: ...n Auxiliary connections Insertion force per pole Max 3N or 0 674 lbf Withdrawal force per pole Min 1 5N or 0 337 lbf IN OUT BATT IN connections Solid 2 5mm 12AWG Stranded 2 5mm 12AWG L 7 0 8 0mm 0 27 0 315in Auxiliary connections Solid 0 75mm 18AWG Stranded 0 75mm 18AWG L 7 0 8 0mm 0 27 0 315in NOTES ...

Page 7: ...7 ...

Reviews: