nextys DCW20 Short Form Installation Manual Download Page 3

 

Operating MODE 

UPS Mode 

 

UPS Mode: 

In UPS mode the DCW20 protects a load from unwanted power interruption in 

case of mains failure. An example of UPS connection is given on to the side.  

When the input is present DCW20 acts as a bypass, connecting the input to the 

output via the input switch. Meanwhile, if required, the battery is charged. 

During bypass there is no voltage conversion, therefore the output supply voltage 

is equal to the input voltage.  

In case of power outage, the DCW20 takes energy from the battery to keep the 

output regulated at “

Nominal output voltage

”. 

 

Backup: 

The system is in backup mode if the supply for the output is sourced from the 

battery (input supply missing). During backup the battery is monitored 

continuously to prevent over discharge.  

A programmable backup timer is also implemented in order to fix a maximum 

backup time during power outages. This allows preserving the battery life and 

shortening the recharge time, avoiding discharging the battery when not needed.  

During backup the internal Coulomb counter is used to give an estimate of the 

residual charge of the battery.  

Backup starts when the output voltage is lower than 90% of the “

Nominal output 

voltage

”. 

 

Battery charger:

 

The battery charger supports 

various chemistries 

such Lead-Acid, Nickel, Lithium 

and Super-capacitors. Other charging algorithms can be implemented by request 

(contact factory).  

The battery charger automatically reduces the current to avoid exceeding the 

maximum input current in case of high current load. 

 

Warnings:

  

- In order to avoid potentially hazardous situations including fire hazard, safety recommendations must be followed. Only authorized staff can install the unit. 

 

- For Lithium cells the balancing and protection circuit must be included in the battery pack. 

 

- For Nickel batteries the use of the external temperature sensor is mandatory. The sensor must be placed in contact with the battery.

 

 

DC-DC Mode 

 

 

 

DC-DC Mode: 

DCW20 can be used as a high performance DC/DC converter. An example of 

DC/DC connection is given on to the side.  

Any voltage between 10V to 55V can be converted to any voltage between 10V 

to 55V (step-up and step-down operation) with up to 20A input or output 

current.  

Input and output are protected against over current with user settable limits.  

When used as a DC/DC converter the input supply must be connected to the 

battery connector as shown on to the side.  

 

Additional Functions 

Battery health monitor 

 

Internal resistance measurement:

 The resistance is periodically measured. The internal resistance is a good indicator of the battery health status; a sudden increase 

of the internal resistance indicates a potential problem on the battery or on the battery wiring. 

 

Temperature measurement

: The battery temperature is monitored through an optional temperature sensor (P/N: WNTC-2MT). The battery charger takes into 

account the battery temperature and provides a temperature compensated charging voltage. In case of over or under temperature the system disconnects the 

battery to prevent damage. 

 

Coulomb counter

: Estimates the remaining battery capacity and consequently the available backup time. 

 

Deep discharge protection

: It protects against the deep discharge of the battery which can lead to its irreversible damage. 

 

Cold Start:

 

The cold start is a procedure that allows turning ON the UPS without the input power. This procedure is used to turn ON the UPS to operate during a power interruption. 

This practice is also a method to see if the battery connected to the DCW20 is functional. In cold start the DCW20 will remain ON for at least 60 seconds independently 

from the battery voltage being under the deep discharge threshold, the inhibit input and the backup timer. After the first 60 seconds the device stays ON until the battery 

is not deep discharged, the backup timer is not expired or the inhibit input is not active. If the input supply returns during cold start the device reverts to normal 

operation.  

To cold start the DCW20: 

 

Press and hold simultaneously the   and   buttons until you see the welcome message on the screen. On the status screen the "Cold start” text is written beside 

the input icon. 

 

Release the buttons. 

 

PC shutdown and automatic restart: 

 

PC shutdown: 

In case the DCW20 is used to supply a PC it is possible to automatically shut down the PC after an adjustable time of backup. For this the PC must run 

the POWERMASTER application (provided free) and must be connected through Modbus. Optionally POWERMASTER can call a task on the PC before shutting down, 

for example to backup some sensitive data.  

 

Automatic restart: 

DCW20 is able to automatically restart a PC which was powered OFF by mistake, for example in case of the Operating System (OS) crash. The 

Summary of Contents for DCW20

Page 1: ...de mort Le boîtier peut produire des brûlures le laisser refroidir avant de toucher l appareil Ne faire pas pénétrer des liquides ou des corps étrangers dans l appareil Pour éviter des étincelles ne pas connecter ou déconnecter l équipement jusqu à ce que la tension d entrée a été supprimée et avant qu il n ait eut lieu la décharge des condensateurs internes minimum 1 minute INTENDED USE USO PREVI...

Page 2: ...lso possible through RS485 connection 6 Inhibit input A voltage between 5VDC and 30VDC applied to this input activates the inhibit function 7 Auxiliary output supply Maximum 5A supply from the battery unregulated 8 Input connection 2 poles are provided for input connection This must be connected to a power supply rated 12 48VDC 9 Output connection 2 poles are provided for output connection It must...

Page 3: ...h user settable limits When used as a DC DC converter the input supply must be connected to the battery connector as shown on to the side Additional Functions Battery health monitor Internal resistance measurement The resistance is periodically measured The internal resistance is a good indicator of the battery health status a sudden increase of the internal resistance indicates a potential proble...

Page 4: ...e optional external sensor exceed the threshold specified in Battery max temperature field If active the battery charged is disabled Battery lifetime elapsed Bat lifetime Active when the actual calculated battery lifetime exceeds the threshold specified in Battery lifetime field Battery charge failure Bat charge fail Active when DCW20 could not charge the battery correctly When active the battery ...

Page 5: ...harge 5 User Mounting Dismounting Instructions For DIN rail mounting according to IEC 60715 TH35 7 5 15 Mounting as shown in figure with input terminals on lower side with suitable cooling and maintaining a proper distance between adjacent devices as specified in the User manual Mounting 1 Tilt the unit slightly backwards 2 Fit the unit over the top edge of the rail 3 Slide it downward until it hi...

Page 6: ...n Auxiliary connections Insertion force per pole Max 3N or 0 674 lbf Withdrawal force per pole Min 1 5N or 0 337 lbf IN OUT BATT IN connections Solid 2 5mm 12AWG Stranded 2 5mm 12AWG L 7 0 8 0mm 0 27 0 315in Auxiliary connections Solid 0 75mm 18AWG Stranded 0 75mm 18AWG L 7 0 8 0mm 0 27 0 315in NOTES ...

Page 7: ...7 ...

Reviews: