nextys DCW20 Short Form Installation Manual Download Page 2

 

System Description 

DCW20 is a microprocessor controlled unit that can perform 2 functions:  

1. UPS rated 960W/20A usable in any system rated 12…48Vdc  

2. DC/DC converter (non isolated) rated 960W/20A usable in any combination of IN/OUT voltages 12…48Vdc  

 

For the UPS function you may use 1 battery of 12V, independently of the operating load voltage. For any supply voltages (12…48Vdc) it may use also multiple battery configuration (10…58Vdc). 

DCW20 monitors the voltage coming from a DC power supply and in case of power failure a backup battery is supplying the energy to the load. In normal condition the battery is kept charged by 

an integrated battery charger supporting various battery chemistries.  

As a DC/DC converter (no battery present) the input has to be connected to the battery connector.  

The input voltage is converted to any output voltage as per the set-up. 

Connections and User interface 

 

1

Alarm LED indicator

ON 

when the unit is in backup. Blinks at 1Hz rate in case of 

error.  

2

Modbus RTU over USB

: Used to connect a PC running POWERMASTER or custom 

application for remote monitoring and controlling. Firmware update is also possible 

through USB connection.  

3

Temperature sensor

: Optional temperature sensor (P/N: WNTC-2MT) to measure 

the battery temperature for protection and temperature compensated charge method.  

4

Relays dry contacts

: 2 relays are present for remote monitoring.  

5

Modbus RTU over RS485

: Used to connect a PC running for remote monitoring and 

controlling. Firmware update is also possible through RS485 connection.  

6

Inhibit input

: A voltage between 5VDC and 30VDC applied to this input activates the 

inhibit function.  

7

Auxiliary output supply

: Maximum 5A supply from the battery (unregulated).  

8

Input connection

: 2 poles are provided for input connection. This must be 

connected to a power supply rated 12…48VDC.  

9

Output connection

: 2 poles are provided for output connection. It must be 

connected to the load to be backed up.  

10

Battery connection

: 2 poles are provided for battery connection. This must be 

connected to the battery. Please respect the correct polarity.  

11. Display area: 

provides information regarding the device status.  

12

Control keys: 

4 push buttons are provided to navigate through the menus and to 

select the various functions.  

 

User Interface 

Symbols 

Name 

Function / Description 

 

MENU Key 

Scrolls between menus. 

 

DOWN Key  Scrolls down menus and values. 

 

UP Key 

Scrolls up menus and values. 

 

OK Key 

Confirms selection. 

 

INPUT 

The measured input voltage and current is shown in this section. 

 

OUTPUT 

The measured output voltage and current is shown in this section. 

 

BATTERY 

The battery voltage, current, temperature, resistance and charge are shown in this section. During charging and discharging the symbol 

background color changes to orange and the number of bars drawn inside reflects the charge status. During discharging and charging an 

arrow drawn beside the symbol reflects the direction of the current flowing through the battery, pointing towards the battery during 

charging. Battery section is not present in DC-DC mode. 

 

AUXILIARY 

The measured auxiliary output voltage and current is shown in this section. 

 

MODE displayed 

UPS status screen 

DC-DC status screen 

Alarm screen 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Summary of Contents for DCW20

Page 1: ...de mort Le boîtier peut produire des brûlures le laisser refroidir avant de toucher l appareil Ne faire pas pénétrer des liquides ou des corps étrangers dans l appareil Pour éviter des étincelles ne pas connecter ou déconnecter l équipement jusqu à ce que la tension d entrée a été supprimée et avant qu il n ait eut lieu la décharge des condensateurs internes minimum 1 minute INTENDED USE USO PREVI...

Page 2: ...lso possible through RS485 connection 6 Inhibit input A voltage between 5VDC and 30VDC applied to this input activates the inhibit function 7 Auxiliary output supply Maximum 5A supply from the battery unregulated 8 Input connection 2 poles are provided for input connection This must be connected to a power supply rated 12 48VDC 9 Output connection 2 poles are provided for output connection It must...

Page 3: ...h user settable limits When used as a DC DC converter the input supply must be connected to the battery connector as shown on to the side Additional Functions Battery health monitor Internal resistance measurement The resistance is periodically measured The internal resistance is a good indicator of the battery health status a sudden increase of the internal resistance indicates a potential proble...

Page 4: ...e optional external sensor exceed the threshold specified in Battery max temperature field If active the battery charged is disabled Battery lifetime elapsed Bat lifetime Active when the actual calculated battery lifetime exceeds the threshold specified in Battery lifetime field Battery charge failure Bat charge fail Active when DCW20 could not charge the battery correctly When active the battery ...

Page 5: ...harge 5 User Mounting Dismounting Instructions For DIN rail mounting according to IEC 60715 TH35 7 5 15 Mounting as shown in figure with input terminals on lower side with suitable cooling and maintaining a proper distance between adjacent devices as specified in the User manual Mounting 1 Tilt the unit slightly backwards 2 Fit the unit over the top edge of the rail 3 Slide it downward until it hi...

Page 6: ...n Auxiliary connections Insertion force per pole Max 3N or 0 674 lbf Withdrawal force per pole Min 1 5N or 0 337 lbf IN OUT BATT IN connections Solid 2 5mm 12AWG Stranded 2 5mm 12AWG L 7 0 8 0mm 0 27 0 315in Auxiliary connections Solid 0 75mm 18AWG Stranded 0 75mm 18AWG L 7 0 8 0mm 0 27 0 315in NOTES ...

Page 7: ...7 ...

Reviews: