This product should be installed only by competent personnel trained in good safety practices involving
high voltage electrical equipment. These instructions are not intended as a substitute for adequate
training or experience in such safety practices. These instructions do not attempt to provide for every
possible contingency. Failure to follow these instructions could result in damage to the product and
serious or fatal injury. IMPORTANT : Cable and associated apparatus must be de-energised, locked out,
and tagged prior to product installation.
For installation on a 480TB, 484TB or 489TB tee connector or a 800PB, 804PB
or 809PB coupling connector tightened with a clamping screw
(type 1)
OR
clamping
screw
clamping
screw
OR tightened with a stud and flange nut
(type 2)
OR
CAUTION : Read instructions thoroughly and completely prior to beginning installation.
Installation instructions for separable coupling connector
K800PB/G
Up to 24 kV
Only to be used on copper wire screened cable with extruded semi-conductive screen
and conductors of copper or aluminium.
For installation on a 480TB, 484TB or 489TB tee connector or a
800PB, 804PB or 809PB coupling connector.
M16
flange nut
M16
flange nut
WARNING :
CHANGED INSTALLATION
Page 1 of 14
IS97180-ENG - K800PB/G-CW45-CA0
18 November 2019 - Revision 2
- Supersedes edition of
28 September 2018
IS97180-ENG - K800PB/G
-CW45-
CA0 - Revision 2