Table 4                                                                                   Table 5

S4 - Back-Up 

Hysteresis

Pos 4

Pos 5

Pos 6

1 Volts

OFF

OFF

OFF

1.2 Volts

ON

OFF

OFF

1.4 Volts

OFF

ON

OFF

1.6 Volts

ON

ON

OFF

1.8 Volts

OFF

OFF

ON

2.0 Volts

ON

OFF

ON

2.2 Volts

OFF

ON

ON

2.4 Volts

ON

ON

ON

INTERNAL BATTERY CHARGING & REPLACEMENT:

The MDP internal battery is a sealed lead acid and requires no maintenance. Battery life is typically up to five years, but 

will vary depending on use and operating environment. The battery should be replaced no less frequently than every five 

(5) years to guarantee proper operation of the MDP. (Request part # 591-0712-0)

To determine the age of the battery, check the date code located on top of the battery. The four digits refer to the year and 

month of manufacture. For instance, a unit with a date code of “1035” was manufactured the 35th week of 2010.

To replace the battery first remove power to the MDP input wiring and turn off all 12 Volt loads connected to MDP. Remove 

the fuse from the holder labeled “BATTERY”. To access the battery, loosen and back out the four front Battery Access Plate 

securing screws and remove Battery Access Plate. 

Once the plate is removed, you will see the battery is secured in position by a Locking Plate. Loosen and back out the two 

Locking Plate locking screws. Lift Locking Plate up from bottom and remove battery. When the terminals are exposed, 

disconnect the push on connectors and remove the battery. Reinstall the new battery by lifting up on the Locking Plate 

and sliding the battery partially back into the compartment, re-attach the terminals (confirm proper polarity or damage 

can result) and push the battery all the way back in until the Locking Plate can shut properly. Dispose of the old battery 

properly. Re-tighten the two battery retaining bracket securing screws. Re-install the battery access plate and re-install 

and tighten the four battery access screws. Although the battery is sealed, it is a Lead-Acid type, so there are restrictions 

on its disposal.

S4 – Charger Re-Start Interval

Pos 1

Pos 2

Pos 3

6 Hrs

OFF

OFF

OFF

7 Hrs

ON

OFF

OFF

8 Hrs

OFF

ON

OFF

9 Hrs

ON

ON

OFF

10 Hrs

OFF

OFF

ON

12 Hrs

ON

OFF

ON

24 Hrs

OFF

ON

ON

48 Hrs

ON

ON

ON

Battery Access Plate

Front Screws

Lock Screws

Locking Plate

Battery

Terminals

+

-

CAUTION: Observe correct battery polarity!

8

Fig. 5: Internal Battery Charging & Replacement

Summary of Contents for MDP-25.0

Page 1: ...Materials Provided 3 Installation 3 Mechanical Power Wiring Signal Wiring Motorola Output Settings Default and Optional Operation 4 Status LEDs Disconnect Timer TMR Operation Advanced Settings Backup...

Page 2: ...Fax 714 957 1621 E Mail techservice newmarpower com www newmartelecom com Quick Reference Guide Status LEDs Page 5 Status LED Legend Page 5 D Sub 9 Pin Motorola Interface Page 4 Input Output Wiring P...

Page 3: ...engine is off Allows use of accessory loads per programmed time limit user adjustable while preserving battery for emergency starting Factory default is not active see page 5 Built in LVD Low Voltage...

Page 4: ...nput wires by disconnecting the battery or shutting off the appropriate circuit Note the MDP functions as an uninterruptable power source If electronics are wired directly to the MDP output and the pr...

Page 5: ...on of voltage occurs augmenting voltage to the electronics for 3 seconds If proper primary voltage is not restored within the 3 second time frame input from the vehicle battery disconnects and electro...

Page 6: ...nce the battery voltage reaches approximately 14 2 volts the charging current will start to reduce The voltage will remain at 14 2 volts stage 2 high rate absorption charge until the current to the ba...

Page 7: ...s 5 Note that the TMR feature is disabled if the Ignition IN pin Pin 2 of the D sub 9 pin connector on front panel see Figure 2 is connected to a voltage greater than 2 volts i e battery Back up funct...

Page 8: ...internal battery see table 4 Hysteresis should be set after determined the amount of voltage drop from the DC source vehicle battery to input terminals of the MDP when the intended output load curren...

Page 9: ...battery loosen and back out the four front Battery Access Plate securing screws and remove Battery Access Plate Once the plate is removed you will see the battery is secured in position by a Locking...

Page 10: ...N If a problem persists after you have applied the above outlined solutions or if you have any questions about the installation and proper operation of the MDP 25 0 please contact NEWMAR s Technical S...

Page 11: ...Box 1306 Newport Beach California 92663 Phone 714 751 0488 Fax 714 957 1621 E Mail techservice newmarpower com www newmartelecom com DIMENSIONAL DRAWINGS 6 980 8 460 5 400 4 750 300 6 000 281 x 4 5 79...

Reviews: