P.O. Box 1306
Newport Beach
California 92663
Phone: 714-751-0488
Fax: 714-957-1621
E-Mail: [email protected]
www.newmartelecom.com
9
TEST / TROUBLESHOOTING
Refer to the status LED indicator legend on page 5, which provides diagnostics of what stage the MDP is currently
operating.
1) Testing Battery Back-up Function:
With a load connected to MDP output remove input fuse and confirm load is powered without interruption from MDP
internal battery: The two GREEN LED’s (“CHARGING” & “INPUT CONNECTED”) should extinguish and the AMBER “Back-
up Power” LED will illuminate.
2) Start-up:
When connecting or reconnecting input power to the MDP it is normal for the “INPUT CONNECTED” LED & “BACK- UP
POWER” LED to both illimunate for 2-3 seconds.
3) Charging LED:
a)
It is normal for the CHARGING LED to extinguish when the three stage charger goes in to sleep mode. (Sleep mode
reduces MDP input current draw when the internal battery is full charged.)
b)
If fuses blow repeatedly, this usually indicates a shorted component. Contact NEWMAR for further trouble shooting
advice. Always verify that the replaced fuses are of the correct rating. Use standard ATC fuses. Do no use
slow-blow fuses.
c)
Flashing Red LED - internal charging temperature exceeds 50° C.
FACTORY CONTACT INFORMATION
If a problem persists after you have applied the above-outlined solutions, or if you have any questions about the
installation and proper operation of the MDP-25.0, please contact NEWMAR’s Technical Services Manager:
Phone:
714-751-0488 - From the hours of 7:00 A.M. to 4:30 P.M. weekdays, P.S.T.
Fax:
714-957-1621
Email:
We are happy to consult with you to resolve any problems or questions you may have. If during consultation, it
appears the MDP-25.0 must be returned to the factory for repair we will issue a Return Materials Authorization at that time.
SPECIFICATIONS:
INPUT:
Stand-by:12 VDC, 12.2 ->15.5 VDC, 11.5 minimum input required for start up,
Maximum Input Current: 28.5 Amps (25 Amps max. Load + 3.5 Amps Charger)
Stand-by Current: <40 mA (no load on output, internal battery charged, 3 Stage charger in sleep mode)
OUTPUT:
12 VDC Filtered, Voltage Spike Protected with Back-Up Battery 25 amps Max.
BACK-UP POWER:
12.0 VDC Nominal, from 7 AH internal battery:
5 amps for 60 Minutes
10 amps for twenty Minutes
25 amps for six Minutes
(All the above assuming fully charged battery @ 25° C)
BATTERY:
Sealed Lead Acid, Rechargeable 7.0 AH, 5 Years Typical Life - User Replaceable
INTERNAL CHARGER:
2 Amps, 3 Stage, Temperature Compensated
FILTERING:
Audio through 200 MHz
VOLTAGE SPIKE PROTECTION:
Transient Energy Capability; 100 Joules, 4,000 amps Max
OPERATING TEMPERATURE:
0 - 50° C
SIZE/WEIGHT:
5.75” H x 6.0” W x 8.5” D (14.6 x 15.24 x 51.59 cm) / 9.4 lbs. (4.3 kg)