Figure 2: Mounting Figure 3: Removing
B) Wiring
1. AC Input: Terminal Block (lettered left to right) - Figure 4
a) Earth Ground
b) AC Hot (note: install jumper provided across terminals j1 and j2 for
115 VAC input)
c) Neutral
j1 & j2) Jumper these two terminals for 115 VAC operation and apply
115V hot to term b and neutral to c
Recommended wire size: 16 AWG
2. Output
The unit has dual output circuits: one for connection to the Load, the
other to the back-up battery. Note: the unit has a load priority circuit,
all produced power fi rst is made available to the load with remaining
power made available for battery charging. Both outputs are isolated
from the case.
Battery Output:
two sets of terminals each for plus and minus. Utilize dual wiring when battery location is more than 15 feet
from unit to minimize voltage drop. See page 2 and 3, Section H for programming per battery type.
Output to Load:
two terminals each for plus and minus, utilize dual wiring when load is
more than 15 feet from unit to minimize voltage drop.
Fuse note: We recommend a 25 amp fuse be installed on the hot leg at battery. If using
both sets of battery terminals on DIN UPS (i.e. two pairs of wires, recommended for long
wire runs), connect both hot wires to one side of battery fuse.
Battery/Output wires size (recommended): 14 AWG
Terminal Block maximum wire size (recommended): 10 AWG
C) Alarm Contacts, Form C (Isolated):
Form C Contacts for remote monitor: Activate upon:
a. AC power fail
b. Low battery, or poor battery condition
Figure 5: Output Terminals
Figure 4: AC Input Terminal Block
A
B
Insert screwdriver in
slot of bottom tab and
twist to extend bracket
A
B
Insert screwdriver in
slot of bottom tab and
twist to extend bracket
a b c j1 j2
MIN
MAX
L
N
(3)
(4)
BATTRY
INPUT
BATTERY
CHARGING LEVEL
i
AC
FAIL
LOW BATTERY
OR BATTERY
REPLACEMENT
DIAGNOSIS
BATTERY
START
TIME
BUFFERING
0 1 2
345
67
8 9
A
U
X
3
OUTPUT LOAD
(1)
(2)
BATTERY
SELECTION
AC
FAIL
LOW BATTERY
OR BATTERY
REPLACEMENT
5 6 7 8 9 10
JUMPER FOR
115 Vac
DIN-UPS 24-20
OUTPUT: 24Vdc 20A
INPUT: 115-230Vac
T
E
M
P
P
R
O
B
E
C
O
M
M
O
D
B
U
S
(714) 751-0488
Www.automationdcpower.com
Newport Beach, CA USA
Load
Output
Battery
Output
MIN
MAX
L
N
(3)
(4)
BATTRY
INPUT
BATTERY
CHARGING LEVEL
i
AC
FAIL
LOW BATTERY
OR BATTERY
REPLACEMENT
DIAGNOSIS
BATTERY
START
TIME
BUFFERING
0 1 2
345
67
8 9
A
U
X
3
OUTPUT LOAD
(1)
(2)
BATTERY
SELECTION
AC
FAIL
LOW BATTERY
OR BATTERY
REPLACEMENT
5 6 7 8 9 10
JUMPER FOR
115 Vac
DIN-UPS 12-35
OUTPUT: 12Vdc 35A
INPUT: 115-230Vac
T
E
M
P
P
R
O
B
E
C
O
M
M
O
D
B
U
S
(714) 751-0488
Www.automationdcpower.com
Newport Beach, CA USA