7
FIGURE 2: Typical Battery Wiring
Note: A typical parallel battery wiring scheme
is depicted here. When wiring batteries in parallel,
it is good practice to attach the (+) and (-) leads to
opposite ends of the battery string, as shown. This
contributes to a more even voltage distribution
among the battery plates when charging and
discharging.
Use only stranded copper wire for DC input/output. Refer to the following chart for the
proper wire size depending on inverter/charger model and the length of wire required*:
Wire Size Chart
Model
Length of Wire from Charger to Batteries (in feet)
10'
15'
20'
Over 20'
Minimum Wire Gauge (AWG)
12-1800IC
#1
#0
#2/0
Not Recommended
12-1801 ICF
#1
#0
#2/0
Not Recommended
12-2500IC
#2/0
#2/0
#2/0
Not Recommended
24-2200IC
#4
#4
#4
Not Recommended
24-2201 ICF
#4
#4
#4
Not Recommended
32-2400IC
#4
#4
#4
Not Recommended
*
Meets minimum requirements of ABYC 10% voltage drop table for inverter maximum
input current, 3% voltage drop table for charger maximum output, and allowable
amperage for 105° C rated insulation conductors <50 VDC inside engine space.
Consult ABYC E-9 for lower temperature rated insulated conductors.
CAUTION:
Ensure that leads are properly fused at the battery. (Refer to ABYC recommenda-
tions regarding fuse type and location.) Refer to the chart on the following page for the
proper battery fuse value for each model:
-
+
FUSE
BATTERY (-) NEGATIVE
BATTERY (+) POSITIVE
TEMPERATURE SENSE
INSTALLER
SUPPLIED