- 72 -
Spinner Alarms
Alarm
Description
Trigger
CLF Basic Single
Spinners Not
Responding
“Spinners Not Responding”
Automatic control for spinners must
be enabled� [CLF Mode] [Basic Single]
must be selected� At least one product
bin must be commanded on� Perceived
spinner speed is greater than 30 rpm in
error from [Target Spinner Speed] for a
period of five consecutive seconds or
longer�
CLF Basic
Independent
Spinners Not
Responding
“Spinner Not Responding” + [Spinner
Name]
enabled� [CLF Mode] [Basic
Independent] must be selected� At least
one product bin must be commanded
on� Perceived spinner speed is greater
than 30 rpm in error from [Target Spinner
Speed] for a period of five consecutive
seconds or longer�
Spinners Off
"Stop Application, Spinners Off!"
CLF is enabled, no spinner speed
detected, one or more control channels
is commanded on�
Spinners On
"Turn spinner switch off to prevent
spinners from running!"
Upon system start up, [CLF Mode]
enabled, spinner functionality switch
detected in the ON position�
Controller Operations