- 43 -
Register
address
Relative
address
(hex)
Register name
Read (R) or
Write (W)
Data
type
Data contents
4: %LEL
Response example: 0x0001 when code
is 1 (ppm).
40013
C
Sensor unit Mfg.
No.(1st and 2nd
letters)
R
Word
Read sensor unit Mfg. No. (8-letter
ASCII code)
Response example: When Mfg. No.
is ”C302026”, 1st letter is “C”, 2nd is “3”,
3rd is “0, …. 7th is “6” and 8th is
“(space)”
“C”=0x43 (high-order byte of word data)
“3”= 0x33 (low-order byte of word data)
“0”= 0x30 (high-order byte of word data)
“2”= 0x32 (low-order byte of word data)
“0”= 0x30 (high-order byte of word data)
“2”= 0x32 (low-order byte of word data)
“6”= 0x36 (high-order byte of word data)
“(space)”= 0x20 (low-order byte of word
data)
40014
D
Sensor unit Mfg.
No.(3rd and 4th
letters)
R
Word
40015
E
Sensor unit Mfg.
No. (5th and 6th
letters)
R
Word
40016
F
Sensor unit Mfg.
No.(7th and 8th
letter)
R
Word
40017
10
Test mode on/off
R
Word
Read current test mode status
ON: 0x0001
OFF: 0x0000
40018
11
Test gas
concentration
R
Word
Read test gas concentration value
Response example: 0x0019 when test
gas concentration is 25%
40019
12
Sensor current
value
R
Word
Read sensor current value
Range: 2.00 to 6.00 mA
Multiplied by 100, then converted to hex
to create the data to send.
Response example: 0x00C8 in case of
200 (2.00 mA)
40020
13
f-value
R
Word
Read sensor unit f-value (4 letter hex
ASCII)
Multiplied by 100, then converted to hex
to create the data to send.
Response example: 0x064 in case of
100 (f-value is 01.00)
40021
14
Calibration gas
code (1st and 2nd
letters)
R
Word
Read calibration gas code (3-letter
ASCII code)
Response example: “0x2D”, “0x2D”,
“0x2D” and “0x20” when code is - - -
plus space.
40022
15
Calibration gas
code (3rd and 4th
letters)
R
Word
40023
16
Calibration gas
concentration
R
Word
Read calibration gas concentration
value
Response example: 0x004B when the
gas concentration value is 75%
40025
18
Linear table X1Y1
R
Word
Read linear table (X1,Y1)
Response example: