Before installing a UX chassis, verify that your installation site meets the following requirements:

Restricted Access Area
Chassis Mounting Space
Equipment Rack
Power Connections

United States and Canada
Europe

Grounding Connections

United States and Canada Grounding Connections
Europe Grounding Connections

Restricted Access Area

UX Series equipment must be installed in restricted access areas such as dedicated equipment room, or electrical closet, in accordance with Articles
110-26 and 110-27 of the 1999 United States National Electrical Code ANSI/NFPA 70.

 is a location for equipment where both of the following apply:

RESTRICTED ACCESS LOCATION

Access can only be gained by service persons or by users who have been instructed about the reasons for the restrictions applied to the location
and about any precautions that shall be taken; and
Access is through the use of a tool or lock and key, or other means of security, and is controlled by the authority responsible for the location.

Chassis Mounting Space

To ensure proper chassis cooling, allow a minimum of 3 inches (7.5 cm) horizontal (side-to-side) clearance between the chassis and any adjacent
equipment. Allow a minimum clearance of 32 inches (81 cm) behind the chassis for proper insertion and extraction of interface cards and power
supplies. There are no clearance requirements above or below the chassis. More than one chassis can be mounted in a standard seven (7) foot rack.
These space requirements must be met to comply with Telcordia and Euro ISDN (ETSI) standards.

When installing the chassis, allow space around the chassis for proper air flow through the unit. 

 on either

Do not block the air vents

side of the UX system to ensure proper cooling of the unit.

To ensure proper cooling, the heat and exhaust generated by adjacent equipment must be considered when installing the UX chassis.

The air inlet is on the left side. The air exhaust for the power supplies is towards the rear. The air exhaust for the rest of the system is
towards the right side of the chassis.

Equipment Rack

UX Series rack-mounted equipment requires an EIA-standard 19 inch equipment rack with either 4 posts or 2 posts.

4-Post Rack Depths
Mounting equipment is provided for 4-post equipment racks with a depth of 24 or 30 inches.

Power Connections

Provide AC power of nominal 120V/60Hz or 240V/50Hz for the equipment rack or shelf where the UX system is installed. For each line feed supplied to
the rack or shelf, a dedicated primary branch circuit protection is required.

UX Series equipment must be provided with dedicated branch circuit protection as a means of disconnecting the (electric) main to
ensure the proper operation of and the safety of the persons servicing and operating this equipment. Therefore, the customer must
provide an external circuit breaker that conforms to local electrical codes.

Power connections to UX Series equipment must be provided from branch mains installed by a trained service personnel. For minimum wire

Summary of Contents for SBC 2000

Page 1: ...NET Confidential Copyright 2011 Network Equipment Technologies Inc All Rights Reserved NET UX SYSTEMS Unified Communications Exchange Customer Documentation DRAFT September 2011...

Page 2: ...Branch Appliance ASM 14 1 5 2 2 Digital Signal Processing DSP Modules 15 1 5 3 Safety Precautions 15 1 5 3 1 Electrostatic Discharge ESD Precautions 16 1 5 4 Safety Requirements 17 1 5 4 1 Power Conn...

Page 3: ...Solution Module ASM Digital Signal Processing DSP Modules Safety Precautions Electrostatic Discharge ESD Precautions Safety Requirements Power Connection Requirements Restricted Access Location Requir...

Page 4: ...cipating in a peer relationship The normal state of this LED is off 4 Ready Status LED This status LED indicates if the UX system is ready to process calls The normal state of this LED is on and green...

Page 5: ...s LED 4 Alarm Alarm Status LED 5 Peer Node Peer Node Status LED 6 Ready Ready Status LED 7 Admin System Administration Ethernet Port 8 Port 1 Primary Application Ethernet Port 1 9 Ports 2 4 Ethernet P...

Page 6: ...er Interface Description Monitor Tab Tasks Tab Settings Tab Logs Tab System Tab UX System Hardware Reference This section contains physical and electrical specifications for the chassis and expansion...

Page 7: ...E1 PSTN Interface Cards Compliance and Regulatory Information This section provides various compliance and regulatory information related to the safety and operation of the UX product Declaration of...

Page 8: ...ty Information Product Emission Class The UX system is a Class A product In a domestic environment this product may cause radio interference in which case the user may be required to take adequate mea...

Page 9: ...otection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can create radio frequency energy and if not installed and used in ac...

Page 10: ...limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio freque...

Page 11: ...ACTA adapted ANSI TIA 968 B standard or it must be connected through protective circuitry that is approved by N E T and registered in accordance with the ACTA adapted ANSI TIA 968 B standard Newly Es...

Page 12: ...ith you distributor as to the surge protector requirements for your equipment Industry Canada Equipment Attachment Limitations The following notices are required by Industry Canada Terminal Attachment...

Page 13: ...telephone line Excessive RENs on the telephone line may result in the devices not ringing in response to an incoming call In most but not all areas the sum of RENs should not exceed five 5 0 To be ce...

Page 14: ...s using N E T products with programmed dialer features stay on the line and briefly explain to the dispatcher the reason for the call before hanging up Perform these activities in off peak hours such...

Page 15: ...cause hardware components to overheat and fail Unauthorized removal of the top panel will void your product warranty and service agreement Application Solution Module ASM Digital Signal Processing DS...

Page 16: ...ectrical situations in the following topics AC Power Electrical AC Power The following information provides safety precautions to follow when using this equipment Always disconnect the power source to...

Page 17: ...unding strap connected to a proper ground when handling modules Keep boards in their antistatic protection bags until you are ready to install them Do not touch pins leads or solder connections on the...

Page 18: ...e consideration of equipment nameplate ratings should be used when addressing this concern e Reliable earthing of rack mounted equipment should be maintained Particular attention should be given to su...

Page 19: ...ation PVC Conductor Stranded Europe Requirements Minimum Wire Size 1 63 mm Minimum Voltage Rating 300 V Insulation PVC Conductor Stranded Use only the AC power cord s supplied with the UX system After...

Page 20: ...ating 300 V Conductor Stranded Europe Grounding Connections Requirements Minimum Wire Size 1 63 mm Minimum Voltage Rating 300 V Conductor Stranded Connecting the UX Chassis to Earth Ground When instal...

Page 21: ...urce This section describes the dimensional environmental power and network specifications and requirements for the UX2000 System Dimensions and Weight Environmental Ranges Operation and Storage Power...

Page 22: ...Replace the UX1000 power supply units with NET provided units only Specifications Specifications The UX system comes equipped with a single power supply which complies with the following specification...

Page 23: ...UX power supplies are tested and certified to meet UL cUL IEC 60950 1 safety requirements For more information about the UX power supply units see UX2000 Power Supplies Networking Interfaces The UX200...

Page 24: ...PSTN Interface Cards Inserting and Removing Interface Cards This section describes the steps for inserting and removing from the rear of the UX chassis Interface Cards Review and follow the UX before...

Page 25: ...o Insert an Interface Card Carefully insert the card so that the left and right edges slide into the mounting slots Grip the outside of the attachment levers and push toward the inside of the card unt...

Page 26: ...rd has board mounted protection circuits for electrical isolation and protection against power crossing lightning surges and hazardous voltages Card Port Versions Port Status LEDs Hot Swap Status LED...

Page 27: ...icates the port has a Loss Of Framing LOF error A cable is connected but UX can not detect a correct T1 or E1 frame Amber Yellow Indicates there is a problem with the far end connection This status is...

Page 28: ...ation Warnings Preparing for Installation Installing the UX Chassis in a 4 Post Equipment Rack Installing the UX Chassis in a 2 Post Equipment Rack Installing Interface Cards Installing Ground Wire Po...

Page 29: ...he UX Chassis in a 4 Post Equipment Rack The UX2000 chassis can be installed in a standard 19 inch 4 post equipment racks Mounting hardware is provided for racks with 24 inch and 30 inch depths Before...

Page 30: ...ng ears securely to the front corners of the UX chassis Attach the 2 pan handle plates securely to the rear corners of the UX chassis Working with a partner lift the UX chassis and slide it into the e...

Page 31: ...000 chassis using only the rack ears attached to the front corners on a 2 post equipment rack Mounting the chassis using only the front mount rack ears will not provide adequate mechanical support and...

Page 32: ...face Cards You must power down the UX system before installing or removing Interface Cards Hot swapping of Interface Cards is not supported in UX 1 2 To Insert an Interface Card Carefully insert the c...

Page 33: ...on of the UX chassis connect the grounding wire and power cables To Install the Grounding Wire and Power Cables Connect a grounding wire to the grounding bolt on the left side of the rear panel in acc...

Page 34: ...ment Bracket Place the cable management bracket on top of the pan handle plates If you have installed the UX chassis in a 2 post configuration you must install the pan handle plates on the rear corner...

Page 35: ...assis can be mounted in a standard seven 7 foot rack These space requirements must be met to comply with Telcordia and Euro ISDN ETSI standards When installing the chassis allow space around the chass...

Page 36: ...lding ground network For ground wire specifics see the tables below for the United States Canada and Europe Only qualified service personnel should perform the electrical procedures for grounding wire...

Page 37: ...he chassis More than one chassis can be mounted in a standard seven 7 foot rack These space requirements must be met to comply with Telcordia and Euro ISDN ETSI standards When installing the chassis a...

Page 38: ...he building ground network For ground wire specifics see the tables below for the United States Canada and Europe Only qualified service personnel should perform the electrical procedures for groundin...

Reviews: