8
(3) Toggle turn on/off switch button
Downlink: 9273000000000000000000
(4) Clear the historical electrical energy data
Downlink:9373000000000000000000
(5) Setting Min Interval = 2 seconds, Max Interval = 300 seconds, Current Change = 100mA,Power Change = 20W
Downlink:01730002012C0064001400
Response: 8173000000000000000000 (successful)
(6) Read the current report interval
Downlink: 0273000000000000000000
Response:82730002012C0064001400
5.3 Example for MinTime/MaxTime logic
Example#1
based on MinTime = 1 Hour, MaxTime= 1 Hour,
PowerChange=2W
MaxTime MaxTime
(MinTime)
(MinTime)
0H 1H 2H
Note:
MaxTime=MinTime. Data will only be report according to MaxTime (MinTime) duration regardless PowerChange value.
Example#2
based on MinTime = 15 Minutes, MaxTime= 1 Hour,
PowerChange=2W
MaxTime
MinTime
MinTime MinTime
MinTime
0H
15
th
M 30
th
M 45
th
M
1H
2H
Collects data
REPORTS 35W
Collects data
REPORTS 39W
Collects data
REPORTS 50W
Collects data
REPORTS 10W
Collects data
REPORTS 11W
Collects data
9W
Does not report
Collects data
10W
Does not report
Collects data
9W
Does not report