6
Example for Report Configuration:
Fport
:
0x07
(1) Configure the device report parameters MinTime = 1min, MaxTime = 1min, BatteryChange = 0.1v
Downlink: 019F003C003C0100000000
The device returns:
819F000000000000000000 (The configuration succeeded)
819F010000000000000000 (The configuration failed)
(2) Read the device configuration parameters
Downlink: 029F000000000000000000
The device returns:
829F003C003C0100000000 (current configuration parameters)
Example for MinTime/MaxTime logic:
Example#1
based on MinTime = 1 Hour, MaxTime= 1 Hour, Reportable Change i.e. BatteryVoltageChange=0.1V
MaxTime MaxTime
Sleeping(MinTime)
Sleeping(MinTime)
Note: MaxTime=MinTime. Data will only be report according to MaxTime (MinTime) duration regardless BatteryVoltageChange value.
Description
Device
CmdID
DeviceType
NetvoxPayLoadData
ConfigReportReq
R718VA
0x01
0x9F
MinTime
(2bytes Unit:s)
MaxTime
(2bytes Unit:s)
BatteryChange
(1byte Unit:0.1v)
Reserved
(4Bytes,Fixed 0x00)
ConfigReportRsp
0x81
Status
(0x00_success)
Reserved
(8Bytes,Fixed 0x00)
ReadConfigReportReq
0x02
Reserved
(9Bytes,Fixed 0x00)
ReadConfigReportRsp
0x82
MinTime
(2bytes Unit:s)
MaxTime
(2bytes Unit:s)
BatteryChange
(1byte Unit:0.1v)
Reserved
(4Bytes,Fixed 0x00)