6. IR Disable Time and Detection Time 

If there are movements of people, animals or any organism in the detected area, the infrared sensor detects the infrared signal.   

And, if the closing event happen in the following 10seconds, the device will report occupy status=1. 

After IRDetectionTime(Default 30s), if there is to no longer people, animals or any organism movement detected by the R718PQA 

within the monitoring range and the reed switch status is detected as open, the device will report occupy status=0. 

 

To save the power, when R718PQA detects the infrared signal, it will enter IRDetectionTime period. If there is no infrared signal 

detected in IRDetectionTime period. It will report un-occupy. 

IRDisableTime is the sampling period during IRDetectionTime (IRDisableTime are 30 seconds by default setting that PIR is off 

for first 70% of the period; on for rest 30% of the period). 

 

For example, after triggered, the PIR will turn off the infrared probe for 21 (30 * 70%) seconds to save the power, living objects 

within this period will not be detected. PIR will re-open detection function after 21 seconds, if it detects living objects in this 

period, the IR delay time will be extended for another 30 seconds till no infrared signal is detected and IRDetectionTime period is 

due and R718PQA will then report un-occupy 

 

Note

IRDisableTime >=5 s, IRDetectionTime>= IRDisableTime 

Default disabletime

30s    detectiontime

5min 

 

Example1: 

The IRDetectionTime is 60 seconds and the IRDisableTime is 30 seconds, no living creature is detected during the two 9-second 

detection period (the yellow parts shown below). R718PQA will report “unoccupied” after 60 seconds (IRDetectTime). 

 

Example2: 

The IRDetectionTime is 60 seconds and IRDisableTime is 30 seconds, living creature is detected at the 25th second of the first 30 

seconds. R718PQA will restart the IR detecting procedure (IRDetectionTime). 

No living creature is detected during the next IRDetectionTime and R718PQA therefore report “unoccupied.” 

 

Note: Occupancy status (status =1) requires both reed switch and infrared to detect close/someone and interval between both less than 10 seconds. 

 

Summary of Contents for R718PQA

Page 1: ...Co Ltd This document contains proprietary technical information which is the property of NETVOX Technology It shall be maintained in strict confidence and shall not be disclosed to other parties in whole or in part without written permission of NETVOX Technology The specifications are subject to change without prior notice ...

Page 2: ... Example of ReportDataCmd 6 5 2 Example of ConfigureCmd 6 5 3 Example for MinTime MaxTime logic 8 6 IR Disable Time and Detection Time 10 7 Information about Battery Passivation 11 7 1 To determine whether a battery requires activation 11 7 2 How to activate the battery 11 8 Important Maintenance Instruction 12 ...

Page 3: ...odulation method greatly increases to expand the communication distance Widely used in long distance low data wireless communications For example automatic meter reading building automation equipment wireless security systems industrial monitoring Main features include small size low power consumption transmission distance anti interference ability and so on LoRaWAN LoRaWAN uses LoRa technology to...

Page 4: ...ameters can be configured through third party software platforms data can be read and alarms can be set via SMS text and email optional Available third party platform Actility ThingPark TTN MyDevices Cayenne Low power consumption and long battery life Note Battery life is determined by the sensor reporting frequency and other variables please refer to http www netvox com tw electric electric_calc ...

Page 5: ...on for 5 seconds success The green indicator remains off fail Had joined the network not at factory setting Turn on the device to search the previous network to join The green indicator stays on for 5 seconds success The green indicator remains off fail Fail to join the network when the device is on Suggest to check the device verification information on the gateway or consult your platform server...

Page 6: ...detected every Min Interval Battery change 0x01 0 1V Disable time 30s Detection time 5min If there is special custom shipment the setting is changed according to customer s requirements IRDisableTime must 5 s and IRDectionTime IRDisableTime Occupancy alarm If there are movements of people animals or any organism in the detected area the infrared sensor detects the infrared signal And if the closin...

Page 7: ...voxPayLoadData Fixed bytes Fixed 8bytes Uplink 0197012201000000000000 Byte Value Attribute Result Resolution 1st 01 Version 1 2nd 97 DeviceType 97 3rd 01 ReportType 1 4th 22 Battery 3 4v 22 HEX 34 DEC 34 0 1v 3 4v 5th 01 Status on 6th 11th 000000000000 Reserved 5 2 Example of ConfigureCmd FPort 0x07 Bytes 1 1 Var Fix 9 Bytes CmdID DeviceType NetvoxPayLoadData CmdID 1 byte DeviceType 1 byte Device ...

Page 8: ...s Reserved 8Bytes Fixed 0x00 Get IRDisableTImeReq 0x04 Reserved 9Bytes Fixed 0x00 Get IRDisableTImeRsp 0x84 IRDisableTime 2bytes Unit s IRDectionTime 2bytes Unit s Reserved 5Bytes Fixed 0x00 1 Configure device parameters MinTime 1min MaxTime 1min BatteryChange 0 1v Downlink 0197003C003C0100000000 Device returns 8197000000000000000000 configuration succeeded 8197010000000000000000 configuration fai...

Page 9: ...ange 0 1V MaxTime sleeping sleeping 0H 15th M 30th M 45th M 1H 1H 10th M 1H 25th M 1H 40th M 1H 55th M 2H 10th M Wakes up and collects data 3 6V Does not report Wakes up and collects data 3 6V Does not report Wakes up and collects data 3 6V Does not report Wakes up and collects data REPORTS 3 6V Wakes up and collects data REPORT 3 6V Wakes up and collects data REPORTS 3 6V Wakes up and collects da...

Page 10: ...ts according to MinTime interval If the data variation is not greater than the last data reported the device reports according to MaxTime interval 3 We do not recommend to set the MinTime Interval value too low If the MinTime Interval is too low the device wakes up frequently and the battery will be drained soon 4 Whenever the device sends a report no matter resulting from data variation button pu...

Page 11: ...1 30 70 seconds to save the power living objects within this period will not be detected PIR will re open detection function after 21 seconds if it detects living objects in this period the IR delay time will be extended for another 30 seconds till no infrared signal is detected and IRDetectionTime period is due and R718PQA will then report un occupy Note IRDisableTime 5 s IRDetectionTime IRDisabl...

Page 12: ...ge period is more than one month from the date of battery production all the batteries should be activated If encountering the situation of battery passivation users can activate the battery to eliminate the battery hysteresis ER14505 Battery Passivation 7 1 To determine whether a battery requires activation Connect a new ER14505 battery to a resistor in parallel and check the voltage of the circu...

Page 13: ...melt some plastic parts Do not store the device in places that are too cold Otherwise when the temperature rises to normal temperature moisture will form inside which will destroy the board Do not throw knock or shake the device Rough handling of equipment can destroy internal circuit boards and delicate structures Do not clean the device with strong chemicals detergents or strong detergents Do no...

Reviews: