6
Description
Device CmdID DeviceType
NetvoxPayLoadData
ConfigReportReq
R718J
0x01
0x21
MinTime
(2bytes Unit:s)
MaxTime
(2bytes Unit:s)
BatteryChange
(1byte Unit:0.1v)
Reserved
(4Bytes,Fixed 0x00)
ConfigReportRsp
0x81
Status
(0x00_success)
Reserved
(8Bytes,Fixed 0x00)
ReadConfigRepor
tReq
0x02
Reserved
(9Bytes,Fixed 0x00)
ReadConfigRepor
tRsp
0x82
MinTime
(2bytes Unit:s)
MaxTime
(2bytes Unit:s)
BatteryChange
(1byte Unit:0.1v)
Reserved
(4Bytes,Fixed 0x00)
(1)
Configure device parameters MinTime = 1min, MaxTime = 1min, BatteryChange = 0.1v
Downlink: 0121003C003C0100000000 003C(H
ex)
= 60(D
ec)
Device returns:
8121000000000000000000 (configuration is successful)
8121010000000000000000 (configuration failed)
(2)
Read device parameters
Downlink: 0221000000000000000000
Device returns:
8221003C003C0100000000 (current device parameters)
Example for MinTime/MaxTime logic:
Example#1
based on MinTime = 1 Hour, MaxTime= 1 Hour, Reportable Change i.e. BatteryVoltageChange=0.1V
MaxTime MaxTime
Sleeping(MinTime) Sleeping(MinTime)
Note:
MaxTime=MinTime. Data will only be report according to MaxTime (MinTime) duration regardless BtteryVoltageChange
value.
Wake up and collects data
REPORTS 3.6V
Wakes up and collects data
REPORTS 3.6V
Wakes up and collects data
REPORTS 3.6V