12
7. Data Report
When the device is turned on, it will immediately send a version package.
➢
Default setting:
Max Interval: 0x0E10 (3600s)
Min Interval: 0x0E10 (3600s)
Battery Change: 0x01 (0.1V)
Temperature Change: 0x0064 (1°C),
Signed 2 Bytes, unit: 0.01°C
Humidity Change: 0x14 (10%),
1 Byte, unit: 0.5%
Illuminance Change: 0x64 (100 lux), 1 Byte, unit:1 lux
Internal Shock Sensor Sensitivity: 0x05 // Internal Vibration Sensor, Sensitivity Range:0x00-0x0A
External Shock Sensor Sensitivity: 0x14 // External Vibration Sensor, Sensitivity Range:0x00-0xFE
(The smaller the number, the more sensitive)
Disabletime: 0x001E (30s) // PIR and
Seat Occupancy (DisableTime must ≥ 5s)
Detechtime: 0x012C (300s) // PIR and
Seat Occupancy (DectionTime must ≥ DisableTime)
AlarmONTime: 0x0F (15s) // Buzzer
Dry Contact Point Out Type: 0x00 (Normally Open)
RestoreReportSet: 0x00 (DO NOT report when sensor restore) // Vibration Sensor
➢
The device report interval will be programmed based on the default firmware.
➢
The interval between two reports must be the minimum time.
➢
The reported data is decoded by the Netvox LoRaWAN Application Command document and