6
FPort
:
0x07
Bytes
1 Bytes
1 Bytes
Var (Fix =9 Bytes)
CmdID
DeviceType
NetvoxPayLoadData
CmdID
– 1 byte
DeviceType
– 1 byte – Device Type of Device
NetvoxPayLoadData
– var bytes (Max=9bytes)
(
1
)
Command Configuration:
MinTime = 1min,MaxTime = 1min,BatteryChange = 0.1v,SensorDisableTime = 30s,SensorDectionTime = 30s
Downlink: 015A003C003C01001E001E 003C(Hex) = 60(Dec) ; 001E(Hex) = 30(Dec)
Response:
815A000000000000000000
(
Configuration success
)
815A010000000000000000
(
Configuration failure
)
(
2
)
Read Configuration:
Downlink: 025A000000000000000000
Response:
825A003C003C01001E001E
(
Current configuration
)
Description
Device
Cmd
ID
Device
Type
NetvoxPayLoadData
Config
ReportReq
R313WA
0x01
0x5A
MinTime
(2bytes Unit:s)
MaxTime
(2bytes Unit:s)
BatteryChange
(1byte Unit:0.1v)
Sensor
DisableTime
(2bytes Unit:s)
Sensor
DectionTime
(2bytes Unit:s)
Config
ReportRsp
0x81
Status
(0x00_success)
Reserved
(8Bytes,Fixed 0x00)
ReadConfig
ReportReq
0x02
Reserved
(9Bytes,Fixed 0x00)
ReadConfig
ReportRsp
0x82
MinTime
(2bytes Unit:s)
MaxTime
(2bytes Unit:s)
BatteryChange
(1byte Unit:0.1v)
Sensor
DisableTime
(2bytes Unit:s)
Sensor
DectionTime
(2bytes Unit:s)