5
5.Data Report
Data report configuration and sending period are as following:
5.1 Example of ReportDataCmd
FPort
:
0x06
Bytes
1
1
1
Var(Fix=8 Bytes)
Version
DeviceType
ReportType
NetvoxPayLoadData
Version
– 1 byte –0x01
——
the Version of NetvoxLoRaWAN Application Command Version
DeviceType
– 1 byte – Device Type of Device
The devicetype is listed in Netvox LoRaWAN Application Devicetype doc
ReportType
– 1 byte –the presentation of the NetvoxPayLoadData
,
according the devicetype
NetvoxPayLoadData
– Fixed bytes (Fixed =8bytes)
Min. Interval
(Unit:second)
Max. Interval
(Unit:second)
Reportable Change
Current Change
≥
Reportable Change
Current Change
<
Reportable Change
Any number between
1~65535
Any number between
1~65535
Can not be 0.
Report
per Min. Interval
Report
per Max. Interval
After power on, the device will immediately send a version packet report and an attribute packet report.
The device sends data according to the default configuration before any other configuring.
Default Setting:
Maximum time: 900s (15min)
Minimum time: 900s (15min)
Battery Change: 0x01 (0.1V)
Current Chang:0x02 (2mA)
Note:
1.
The cycle of the device sending the data report is according to the default.
2.
The interval between two reports must be the MinTime
Please refer Netvox LoRaWAN Application Command document and Netvox Lora Command Resolver